Product Specific & Important Safety Information
Model:
PIONEER III
Laboratory:
Underwriter’s Laboratories, Inc.
Report No:
Project 4788732172
Type:
Wood Fireplace
Standard:
UL127-2011 and CAN/ULC-S610-
2018 (A1998) and (UM) 84-HUD,
Manufactured Home Approved.
A. Appliance Certification
C. Mobile Home Approved
This appliance is approved for mobile home installations
when not installed in a sleeping room and when an outside
combustion air inlet is provided. The structural integrity of
the mobile home floor, ceiling, and walls must be main
-
tained. The appliance must be properly grounded to the
frame of the mobile home and use only listed double-wall
connector pipe.
D. Glass Specifications
This appliance is equipped with 5mm ceramic glass.
Replace glass only with 5mm ceramic glass. Please
contact your dealer for replacement glass.
B. BTU & Efficiency Specifications
Hearth & Home Technologies WILL NOT warranty appli
-
ances that exhibit evidence of over-firing. Evidence of
over-firing includes, but is not limited to:
• Warped air tube
• Deteriorated refractory brick retainers
• Deteriorated baffle and other interior components
NOTE:
This installation must conform with local codes. In the
absence of local codes you must comply with the
UL127-2011,
(UM) 84-HUD and NPFA211
in the U.S.A. and the CAN/
ULC
S610-2018 (A1998) and CAN/CSA-B365 Installation Codes
in Canada.
The PIONEER III Wood Appliance meets the U.S. ENVI
-
RONMENTAL PROTECTION AGENCY Certified to comply
with 2020 particulate emission standards using cord wood.
EPA Certified Emissions: 2.0 g/hr
*LHV Tested Efficiency: 74.3%
**HHV Tested Efficiency: 69.1%
***EPA BTU Output: 14,700-72,800/hr
Vent Size: 8 inches
Firebox Size: 4.07 cubic feet
Recommended Log Length: 24 inches
Fuel Seasoned Cord Wood less
than 20% moisture
HHT:
SL300 Series
DuraVent:
DuraPlus
*Weighted average LHV (Low Heating Value) efficiency using
cord wood and data collected during EPA emission test. LHV
assumes the moisture is already in a vapor state so there is no
loss in energy to vaporize.
**
Weighted average HHV (High Heating Value) efficiency us
-
ing cord wood and data collected during EPA emission test.
HHV includes the energy required to vaporize the water in the
fuel.
***
A range of BTU outputs based on HHV (High Heating Value)
and the burn rates from the low and high EPA tests, using cord
wood.
The Pioneer III is Certified to
comply with 2020 particulate
emission standards.
DO NOT:
• install or operate damaged fireplace
• modify fireplace
• install other than as instructed by Hearth & Home
Technologies
• operate the fireplace without fully assembling all
components
• install unvented gas log set
• install any component not approved by Hearth & Home
Technologies
• install parts or components not Listed or approved
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. For
assistance or additional information, consult a qualified
installer, service agency or your dealer.
WARNING! Risk of Fire!
Hearth & Home Technologies
disclaims any responsibility for, and the warranty and
agency listing will be voided by the above actions.