C. Hearth Pad Requirements
(UL and ULC)
EMBER PROTECTION:
It is necessary to install a Type I
floor protector.
Floor protector must be non-combustible material, extending
beneath appliance
with a minimum of 6 inches (152mm) in
front of glass and 6 inches (152mm) to both sides of the
fuel loading door. Open the door and measure 6 inches
(152mm) from the side edge of the opening in the face of
the appliance.
USA INSTALLATIONS
: A
non-combustible floor protection
is recommended extending beneath the flue pipe when
installed with horizontal venting or under the Top Vent
Adapter with vertical installation.
CANADA INSTALLATIONS
: A
non-combustible floor
protection extending beneath the flue pipe is
required
with horizontal venting or under the Top Vent Adapter with
vertical installation.
USA
(from side of
appliance)
2”
13-5/8”
27”
30-1/8”
(from front of
appliance)
6”
Figure 12.1
CANADA
346mm
(from front of
appliance)
152mm
889mm
765mm
152mm
51mm
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble
Figure 12.2
USA
44-9/16”
26-11/16”
13-5/8”
3”
(from front of
appliance)
6”
Figure 12.3
CANADA
346mm
678mm
1132mm
(from front of
appliance)
152mm
Figure 12.4
Fire Risk
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
WARNING