QTS AN-X3-MOD-MAS Скачать руководство пользователя страница 1

 

AN-X3-MOD-MAS 
Modicon S908 
Remote I/O 
Scanner Module

 

 
User Manual 
 

 

 

 

 

 

 

 

 

 

Содержание AN-X3-MOD-MAS

Страница 1: ...AN X3 MOD MAS Modicon S908 Remote I O Scanner Module User Manual...

Страница 2: ...ular installation Quest Technical Solutions does not assume responsibility or liability to include intellectual property liability for actual use based upon the examples shown in this publication Curr...

Страница 3: ......

Страница 4: ...ions 11 QUICK START 12 ETHERNET CONFIGURATION 13 Ethernet Configuration 13 DHCP 14 Static IP Address 14 Hostname 15 Firmware 15 Submitting the Configuration 15 Reconfiguring an AN X from an Unknown St...

Страница 5: ...s 36 Sample Ethernet IP Configuration File 37 SCANNING I O 38 Program Run 38 Required Connections 38 ControlLogix Alias Tags 38 Using the Ethernet IP Log 40 Redundancy 40 ControlLogix Ethernet Configu...

Страница 6: ...53 Submitting the Configuration 53 Diagnostic Capture 53 AN X Firmware Update 54 AN X Module Restart 56 Support Menu 56 TROUBLESHOOTING 57 LEDs 57 Ethernet LEDs 57 SYS or MS LED 57 Railroading SYS or...

Страница 7: ...module supports 800 series and Quantum remote drops It supports up to 32 drops The AN X MOD MAS module has a web interface for configuring the module for monitoring logs diagnostics and I O data and...

Страница 8: ...ect to the S908 remote I O network A watchdog timer is implemented in the module s hardware If the firmware does not kick the watchdog within the timeout period the watchdog times out and places the m...

Страница 9: ...page 16 for details Reinsert the card in the slot at the back of the AN X3 with the pins facing up WARNING If you remove the card to edit the configuration file push the card in straight or the card...

Страница 10: ...er consumption is 150 mA 12VDC or 75 mA 24VDC The part number for the power connector is Phoenix MSTB 2 5 3 ST 5 08 S908 Cabling and Termination Refer to the Modicon Remote I O Cable System Planning a...

Страница 11: ...ect the S908 cable to earth ground If a connection to ground is required use an F connector grounding block Ethernet Cabling AN X has a standard RJ 45 connector for connecting to Ethernet If you are c...

Страница 12: ...work 10 3 Use the web interface to Auto Config the AN X from the attached Modicon network 19 4 Configure the AN X in RSLogix 5000 25 5 Scan I O read inputs and write outputs 38 6 Use the web interface...

Страница 13: ...assign a different IP address each time AN X powers up and any software that accesses the AN X module would have to be reconfigured If you are using multiple AN X modules connect and configure one at...

Страница 14: ...N X3 finds a DHCP server on the network it obtains an IP address and other network parameters netmask and default gateway from the DHCP server To find the address assigned look at the DHCP server When...

Страница 15: ...cores TIP When you configure the AN X in RSLogix 5000 use this same name for the emulated ENBT See page 25 Firmware Select the firmware the AN X is to load from the list provided AN X builds the list...

Страница 16: ...le config txt on the microSD card When you perform the Administration AN X Configuration command from the web interface it writes the results to config txt Each line consists of a keyword followed by...

Страница 17: ...ss 169 254 42 84 using a web browser there are two options for setting the AN X Ethernet parameters Option 1 Edit config txt on the SD card Turn off power to the AN X remove the microSD card insert it...

Страница 18: ...10 10 0 20 20 255 255 255 255 255 255 255 255 10 10 0 20 10 10 0 20 1 Default Gateway 10 10 0 1 Persistent Routes None If there is no entry in the network destination column that starts with 169 254 0...

Страница 19: ...ile using a text editor and send it to the AN X3 MOD MAS Sample RIO and Ethernet IP configuration files are provided as a starting point You can use Auto Config to build an initial configuration file...

Страница 20: ...ormation on how to transfer the configuration from AN X and save it to a file In the RIO Configuration Log the AN X displays the I O modules it has found as well as a summary for each drop that shows...

Страница 21: ...the rack and slot definitions for the drop Begin a rack definition with a line that consists of the keyword Rack followed by an equals sign and then the rack number from 1 to 5 for 800 series drops or...

Страница 22: ...lose communication with the network master To set these modules to hold their last state add a line after the slot definition that contains the keyword CfgOutLast Example Slot 4 Type DRA_840_00 CfgOu...

Страница 23: ...ere should be no spaces before or after the equals sign Example Drop 1 HoldTime 3 Sending and Retrieving Configurations To send an RIO configuration file to the AN X3 MOD MAS first select Automation N...

Страница 24: ...DI_353_00 Addr d4s4 Inp 04 Out 00 DC IN 24V 4x8 Sink Slot 5 Type DDO_353_00 Addr d4s5 Inp 00 Out 04 DC OUT 24V 4x8 CfgLen 2 0x0000 0x0000 Slot 6 Type ACI_030_00 Addr d4s6 Inp 18 Out 00 AN IN 8CH UNIPO...

Страница 25: ...aintaining each connection You map the inputs and outputs for the Modicon I O modules on the S908 network to these scheduled connections AN X can create the mappings automatically or you can create a...

Страница 26: ...Connection to None Set the chassis size to 17 Set the Slot to 16 Set the IP address to match the AN X module Record the Name as it is used to create aliases to access the data Click OK to accept the...

Страница 27: ...e and select New Module From the Other category select 1756 MODULE and click OK Set the Name and Description as desired Set the Comm Format to Data INT Set the other parameters as shown Set the Slot t...

Страница 28: ...from the ControlLogix TIP Use the web interface of the ENBT module that connects to the AN X to view the communication loading of the ENBT module Mapping I O Data You map Modicon input and output dat...

Страница 29: ...e ClxPrefix can be used to distinguish tags for the same Modicon address when the ControlLogix processor has connections to more than one AN X MOD MAS For example if the ControlLogix has connections t...

Страница 30: ...from 1 to 5 for 800 series drops and 1 to 4 for Quantum drops and s is the slot number from 1 to 16 If the rack number is 1 the explicit rack number ry can be omitted Example To associate ControlLogix...

Страница 31: ...cessor is in program mode Similarly ControlLogix processors with exclusive owner connections to other AN X slots will also update If the exclusive owner connection to slot 0 stops AN X stops all commu...

Страница 32: ...ask 9 Error mask for protocol errors To map the diagnostic counters include a line with the keyword DiagCtrs in the input section of a connection This maps all ten diagnostic counters they cannot be m...

Страница 33: ...clude a line with the keyword DropErr If you omit the offset the line must start with a comma Examples DropErr 10 DropErr offset 10 TIP Map the drop error table to the first two words of input data of...

Страница 34: ...t 3 16L 16H 17L 17H 18L 18H 19L 19H 20L 20H 21L 21H 22L 22H 23L 23H Offset 4 24L 24H 25L 25H 26L 26H 27L 27H 28L 28H 29L 29H 30L 30H 31L 31H Offset To map the module status data for a given Quantum dr...

Страница 35: ...start with a comma Examples ConnStats2 40 ConnStats2 offset 40 To clear the connection statistics set bit 0 in word 0 of the output data for connection 15 This clears the diagnostic counters and the c...

Страница 36: ...X3 MOD MAS first select Automation Network Configuration in the web interface Click the Choose File button select the file then click the Send Ethernet IP Config to AN X button to transfer the config...

Страница 37: ...0 AN OUT 4CH CURR 7 d5s3 d05s3_Out Len 4 B872 ANALG 4 CH O B872 11 d5s4 d05s4_Out Len 1 B804 16 OUT B804 DataInput ClxBaseTag Inputs to ControlLogix 0 DropErr Always Map to Ofs 0 Since Logix will set...

Страница 38: ...munication with the S908 network WARNING The ScanModProg option is included for debugging since it allows inputs to update in the ControlLogix It is NOT recommened for normal operation For maximum com...

Страница 39: ...nfiguration Each tag is a ControlLogix alias For example ALIAS MOD_d05s4_Out B804 AnxMod 0 O Data 0 In this example the tag name is MOD_d05s4_Out The name is made up of the ClxPrefix and the tagname f...

Страница 40: ...takes the primary AN X offline and the backup takes over The backup AN X constantly monitors the S908 network When it becomes the primary it has the current state of inputs drop status etc The Contro...

Страница 41: ...ner set bit 0 to 1 To set an AN X to act as a backup set bit 0 to 0 If the configuration file contains RedundEna you must map RedundCtl ScanSts ScanSts is an array of 5 INTs that contain information a...

Страница 42: ...4 DataInput inputarray0 0 DropErr 2 d4s3 d04s3_Inp Len 2 DDI_353_00 DC IN 24V 4x8 Sink 4 d4s6 d04s6_Inp Len 9 ACI_030_00 AN IN 8CH UNIPOLAR 13 d5s3 d05s3_Inp Len 4 B863 REG 4 CH IN B863 ClxSlot 15 Dat...

Страница 43: ...rent master is disconnected from the S908 network even for a very short period the backup will take over When the module that was disconnected comes online both modules will be master on the S908 netw...

Страница 44: ...ge 44 AN X3 MOD MAS Dec 2023 LEDs When the AN X MOD MAS is used in redundant mode the network LED is green when scanning orange when monitoring and red when there has been an error or during switchove...

Страница 45: ...the AN X View the results of the configuration Monitor I O and Ethernet diagnostic counters Configure the Ethernet settings and select firmware Archive the AN X configuration Update the AN X firmware...

Страница 46: ...o a problem where data appears not to have changed flush the cache in the browser or run the browser in the mode where it doesn t cache data incognito in Chrome Private browsing in Firefox and Safari...

Страница 47: ...e format Use the Choose File button to select the file Select Send RIO Config File to AN X or Send Ethernet IP Config to AN X AN X parses the files and displays the configurations and the configuratio...

Страница 48: ...Page 48 AN X3 MOD MAS Dec 2023 Monitor RIO Select Automation Network Monitor RIO to display RIO scanner status diagnostic counters and I O data Checkboxes may be used to choose which drops to display...

Страница 49: ...S Count of times a packet was transmitted to a drop and no reply was received RX OVERRUN Count of received packets with overrun errors RX PACKET SHORT Count of received packets that were shorter than...

Страница 50: ...t of Counter Description TxFrms Count of transmitted frames TxBusy Percentage of time the tranmitter is not idle RxFrms Count of received frames RxBusy Percentage of time the receiver is not idle EthE...

Страница 51: ...t counter reset in ms Log Files AN X maintains various logs to record diagnostic and error messages Use the Log Files menu in the web interface to view these logs Ethernet IP Log The Ethernet IP Log s...

Страница 52: ...ial number and MAC Address of the AN X3 being configured Check either DHCP or Static DHCP If the AN X3 finds a DHCP server on the network it obtains an IP address and other network parameters netmask...

Страница 53: ...ovided AN X builds the list from the firmware files on the microSD card that are compatible with the AN X Modicon hardware Submitting the Configuration Once you have entered all required parameters cl...

Страница 54: ...applications that use the AN X are running Browse to select the file then click the Update Firmware button to transfer the file WARNING It is essential that you do not disrupt power while updating fi...

Страница 55: ...AN X3 MOD MAS Page 55 AN X displays progress and status information as the firmware is updated...

Страница 56: ...ve other files to transfer return to the main page and continue Otherwise restart the AN X in order to run the updated firmware AN X Module Restart Use the AN X Module Restart command to restart the A...

Страница 57: ...d errors Errors or status indication in boot mode cause the LED to flash yellow Otherwise the LED flashes red The SYS or MS LED should be used in conjunction with the logs to locate the cause of probl...

Страница 58: ...of the firmware To set debug mode enter a line withjust the keyword LedModeDebug in the ControlLogix configuration file When you Auto Config the AN X it enables debug mode in the file it creates Stan...

Страница 59: ...Color Meaning Flashing or solid red Network error Yellow No configured Modicon I O Green All configured drops are responding Some modules may be in error Fatal Errors AN X3 monitors its operation for...

Страница 60: ...nning The web page displays the update progress at the bottom left of the page You must restart the AN X3 to run the firmware that you transferred WARNING It is essential that you do not disrupt power...

Страница 61: ...Ethernet and Modicon S908Remote I O network Maximum Power Consumption 150 mA 12 VDC or 75 mA 24 VDC Maximum Power dissipation 1 8W Environmental Conditions Operational Temperature 0 50 C 32 122 F Sto...

Страница 62: ...03 7724 2080 support AP prosoft technology com Europe Middle East Africa Languages Spoken French English 33 0 5 34 36 87 20 support EMEA prosoft technology com North America Languages Spoken English S...

Страница 63: ...iginal identification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables nor to any damage resulting from battery leakage In al...