SMS Lite 4G
–
User Guide
© 2021 QTech Data Systems Ltd
12
Configuration
Program the ‘debounce’ option and value using the following instruction:
#[PIN][space]<object>:<item>=<value>[dot]
#12345 site:debounce=value.
(
e.g #12345 site:debounce=1min)
The value must be written in the following format "0 sec", "5 secs", "10 secs", "30 secs", "1 min", "5
mins", "10 mins", "15 mins"
For example:
#12345
site:debounce=10 secs.
Clearing the configuration settings
To clear all of the SMS Lite configuration settings, use the message:
#[PIN][space]Defaults[dot]
Note: This command will also clear all the programmed telephone numbers
Supply Voltage Alarm
If the SMS Lite supply voltage drops below 10.5V DC, Ph1 will receive this notification message:
The supply voltage at <site> has gone low.
When the voltage increases above 11.5V DC a supply voltage message will be sent:
The supply voltage at <site> has returned to normal.
Operational Commands
Inputs
To acknowledge an alarm:
OK <input name> (
e.g. Text:
OK Pump
)
This will stop any further escalation of the alarm to the numbers in the phone list for that input
status change. It will begin at the top of the list the next time the input is activated.
To force the SMS Lite to send the alarm message to the next phone number in the list.
BUSY
<input name> (
e.g. Text:
BUSY Pump
)
Not available to the last phone number in the list of that input.
Alarm message for one person:
<Site> <Input> has turned ON. (
e.g. Text:
Shed1 Pump has turned ON
)
Supply voltage alarms do not escalate like input alarms. Supply voltage can be queried at any time using the
STATUS command