Figure 6-18
Procedures of Removing the Host Card from the Controller Cage
Figure 6-19
Procedures of Pull out the Host Card and Install Dummy Host Card Cage
Figure 6-20
The Finished Installed Dummy Host Card Cage
6.5.
Removing the Cache-to-Flash Modules
Navigate to the SANOS UI ->
SYSTEM SETTINGS
->
Power
->
Cache to Flash
and view the
status of the power module or flash module. If it shows
Failed
, that means your power
module or flash is not
functioning correctly and can’t provide real time data protection
anymore. You may need to replace the power module or flash to ensure continued
protection. The following figure is the example of a failed flash module.