DCE.230 DC Energy Meter

 

DCE.230 User Manual 1.7

 

 

 

 

1. Introduction

 

DCE.230 series DC energy meters are 
designed for measuring and monitoring 
in DC systems. The din rail DC energy 
meters can measure of important DC 
parameters: Voltage, current, power 
and energy etc. It also support bi-
directional measurement with pulse 
output. All data in the meter are 
accessible via RS485 using Modbus RTU. 
The meter has DC power supply. Input 
voltage range up to 1000V DC, and 
current inputs are flexible with DC shunt 
and current sensors.

 

 

 

Measures kWh, W, V, A etc.

 

 

Bi-directional measurement 
IMP & EXP

 

 

Pulse output

 

 

RS485 Modbus

 

 

Din rail mounting 35mm

 

 

DC shunt connection

 

 

Class 1

 

 

1.1 General Specifications

 

Voltage DC Input: 5~1000V DC

 

Auxiliary Supply: 9-40V DC 

 

DC Shunt Input: 75mV

 

Current Range: 0~2000A

 

Power consumption: ≤ 2W / 5VA

 

AC voltage withstand: 4400V/ 1min

 

Impulse voltage withstand: 6.4kV - 
1.2/50μS waveform

 

 

1.2 Unit Characteristics

 

The Unit can measure and display:

 

 

voltage

 

 

Currents

 

 

Power

 

 

Active energy imported and 
exported

 

Pulse output indicates real-time energy 
measurement. An RS485 output allows 
remote monitoring from another 
display or a computer.

 

 

1.3 Shunt Primary Current

 

The unit can be configured to operate 
with primary current and secondary 
input.

 

Primary current range: 0~2000A.

 

Second input: 75mV

 

 

1.4 RS485 Output for Modbus RTU

 

For Modbus RTU, the following RS485 
communication parameters can be 
configured from the Set-up menu:

 

 

Baud rate 

1200,2400, 4800, 9600,19200 

 

Parity 

none (default)/odd/even

 

Stop bits 

1 or 2

 

RS485 address 

3-digit, 001 to 247

 

 

Modbus™ Word order

 

Hi/Lo byte order 

is set automatically to normal or 
reverse. It cannot be configured

 

from the set-up menu.

 

Set-up screens are provided for setting 
up the RS485 port.

 

 
 

1.5 Pulse output

 

The unit provides a pulse output. The 
constant can be configured to below:

 

Pulse output: 1, 10, 100, 1000 imp/kWh 
(default)

 

Pulse duration: 60, 100 (default), 200mS

 

Pulse output indicate: Total kWh/ 
import kWh/ export kWh

 

Display: LCD with backlit

 

Max. Reading: 999999.9kWh

 

Weight: 220g

 

Standard: GB/T 33708-2017

 

10000 imp/kWh

 

1000 imp/kwh

 

100 imp/kWh

 

10 imp/kWh

 

1 imp/kWh

 

Pulse width: 200/100(default)/60 ms.

 

Note: the relationship between pulse 
constant and CT1

 

CT1

 

Default pulse

 

imp/kWh

 

Settable pulse 
imp/kWh

 

1–20

 

1000 

 

1000,100,10,1 

 

21–200

 

100 

 

100,10,1

 

201–2000

 

10 

 

10,1

 

 

*when the CT setting on meter is 2000A, 
the default pulse constant is 10 
imp/kWh and it can be set to 
10imp/kWh or 1 imp/kWh.

 

 

*Over-current alarm: Alarm will 
happened when the current is over the 
CT1 value set on the meter. The Alarm 
LED will stay solid and the corres-
ponding register value will be changed. 
The user can read this register through 
communication to determine whether 
an overcurrent alarm has occurred.

 

The pulse outputs can be set to generate 
pulses to represent Import kWh/ Export 
kWh/ total kWh.

 

 

The pulse output is passive type, 
complies with IEC62053-31 Class A.

 

 

 

 

1.7 Environment

 

Operating temperature -25 to + 55

 

Reference temperature 23

℃±

2

 

Relative humidity 0 to 90%, non-
condensing

 

Altitude up to 2000m

 

Installation category CATIII

 

Mechanical Environment M1

 

Electromagnetic environment E2

 

Degree of pollution 2

 

 

1.8 Mechanics

 

Din rail dimensions 36x100x63 (WxHxD) 
DIN 43880

 

Mounting DIN rail 35mm

 

Ingress Protection IP51 (indoor)

 

Material Self-extinguishing UL94V-0

 

 

2. Operation

 

2.1 Initialization Display

 

When it is powered on, the meter will 
initialize and do self-checking.

 

 

 

 
 

Full Screen (stay 
2s)

 

 

 

 

Software Version 
(stay 2s)

 

(This information 

 

is for reference 
only.)

 

 

 

 

Current Modbus 
address

 

(stay 2s)

 

 

 

 

Current baud 
rate (stay 2s)

 

 

 

Total active 
energy(kWh)

 

Total= 
Export

 

Max read: 
999999.9 kWh

 

 

 

2.1 Buttons function

 

There are two buttons on the front 
panel.

 

 

>

Scroll

 the display for 

data checking.

 

>Changing option at 
Set-up mode

 

>Exit the Set-up mode

 

 

 

>

Set

-up mode entry

 

>Confirmation

 

 

 

2.1.1 Scroll display

 

After initialization and self-checking 
program, the meter displays the 
measured values. The default page is 
total kWh. If the user wants to check 
other information, please press the 
scroll button on the front panel.

 

 

Total active 
energy(kWh)

 

Total= 
Export

 

Display format:

 

5+2 -> 6+1 -> 5+2

 

99999.99 -> 
100000.0 ->

 

999999.9 -> 
00000.00

 

 

 

Partial resettable 
active

 

energy

 

Display format:

 

5+2 -> 6+1 -> 5+2

 

99999.99 -> 
100000.0 ->

 

999999.9 -> 
00000.00

 

 

 

Voltage

 

 

 

Current

 

 

 

Power

 

Display format:

 

<1000 W: XXX W

 

<1000kW: XXX.XXX 
kW

 

For other value: 
XXXX.XX kW

 

 

 

 

Pulse constant

 

 

 

 

CT1 Primary 
current

 

 

 

 

Meter address

 

 

 

 

Baud rate

 

 

 

 

Parity

 

 

 

 

Software Version

 

 

 

Set-up Mode

 

To get into Set-up Mode, the user need 
press the “Enter” button for 3 second.

 

 

 

1

 

Password

 

To get into Set-up mode, 
it asks a password

 

confirm. Default 
password: 1000

 

Use 

Scroll

 and 

Set

 to 

enter correct password.

 

 

 

Keep pressing 

Set

 for 3 

second, the current 
selection

 

will flash, use 

Scroll

 and 

Set

 to change the 

Modbus address. 
Options: 1~247

 

Keep press 

Set

 for 3s to 

confirm the selection.

 

 

 

3

 Keep pressing 

Set

 for 3 

second, the current 
selection will flash, use 

Scroll

 and 

Set

 to change 

the Baud rate. Options: 
1.2k, 2.4k,4.8k,9.6k ( 
default ),19.2k

 

Keep press 

Set

 for 3s to 

confirm the selection.

 

 