When you input KEB Ride-Thru, KEB operation continues after the time set in
L2-10
is expired. When you
cancel KEB Ride-Thru, the motor accelerates again. When you do not input KEB Ride-Thru during the time set in
L2-10
, the drive accelerates to the frequency reference that the drive had before power loss in the applicable
acceleration time.
When
L2-01 = 1 and L2-50 = 2, 3, or 4
, and the DC bus voltage is a minimum of the value of
L2-11 [KEB DC
Volt Setpoint]
, the drive accelerates again after the time set in
L2-10
is expired. If the DC bus voltage is less than
the
L2-11
value, KEB operation continues after the time set in
L2-10
is expired.
Note:
•
When
L2-01 = 0 [Disabled], or L2-01 = 1 and L2-50 = 0 or 1 [Timer Controlled or While CPU Active]
, increase the value of
L2-10
.
Set
L2-10
to cancel KEB operation if the KEB Ride-Thru is not input
•
Set this parameter to 0 to disable the function.
■
L2-11 KEB DC Volt Setpoint
No.
(Hex.)
Name
Description
Default
(Range)
L2-11
(0461)
Expert
KEB DC Volt Setpoint
Sets the target value that controls the DC bus voltage to a constant level in Single Drive KEB
Ride-Thru 2. Sets the DC bus voltage level that completes the KEB operation for all other KEB
methods.
Determined by E1-01
(Determined by E1-01)
■
L2-29 KEB Method
No.
(Hex.)
Name
Description
Default
(Range)
L2-29
(0475)
Expert
KEB Method
Sets the KEB function operation mode.
1
(1 - 4)
Set
L2-01 = 1 [RideThru@PwrLoss = Enabled], and set L2-50 = 2, 3, or 4 [RidThruMode@PwrLoss = KEB
Mode, KEB Stop Mode, or KEB Decel to Stop]
or
KEB Ride-Thru 1/2 [H1-xx = 40, 41, 42, or 43]
, to enable the
KEB function.
1 : Single KEB1 Ride-Thru
The drive monitors the DC bus voltage and uses regenerative energy from the motor to hold the DC bus voltage at
the level set in
L2-11 [KEB DC Volt Setpoint]
.
The KEB operation continues and the deceleration rate changes as specified by
C1-09 [Fast Stop Time]
.
Note:
•
If the drive detects
Uv1 [DC Bus Undervoltage]
during KEB operation, decrease the value of
C1-09
.
•
If the drive detects
ov [Overvoltage]
during KEB operation, increase the value of
C1-09
.
2 : Single KEB2 Ride-Thru
The drive does KEB operation and automatically calculates the deceleration rate to make sure that the main circuit
electrical energy and main current voltage from motor regenerative energy is equal to
L2-11 [KEB DC Volt
Setpoint]
.
3 : System KEB1 Ride-Thru
The drive does not monitor the DC bus voltage and decelerates as specified by the KEB deceleration time set in
L2-06
.
Set
L2-06
to the time necessary to decelerate from the frequency reference to 0 Hz when the drive detects a
momentary power loss. The drive can decelerate and keep constant deceleration rates for more than one drive.
Note:
If you keep constant deceleration rates for more than one drive, it can trigger
ov
faults. Use the dynamic braking option with System
KEB Ride-Thru 1 to prevent
ov
faults.
4 : System KEB2 Ride-Thru
The drive monitors the DC bus voltage and decelerates for the deceleration time set in
L2-06
.
If the DC bus voltage increases, the drive momentarily holds the frequency to prevent
ov
while deceleration
continues.
Note:
When you cannot use a dynamic braking option, use System KEB Ride-Thru.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...