SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
639
■
E2-10 Motor Iron Loss
No.
(Hex.)
Name
Description
Default
(Range)
E2-10
(0317)
Motor Iron Loss
Sets the motor iron loss.
Determined by o2-04 and
C6-01
(0 - 65535 W)
■
E2-11 Motor Rated Power (kW)
No.
(Hex.)
Name
Description
Default
(Range)
E2-11
(0318)
Motor Rated Power (kW)
Sets the motor rated output in the units from
o1-58 [Mot Capacity Unit]
.
Determined by o2-04, C6-
01
(0.00 - 650.00)
The drive automatically sets this parameter to the value input for
“
Motor Rated Power
”
during Auto-Tuning.
Note:
•
When the maximum applicable motor output ≤ 300 kW, the drive uses 0.01 kW units.
•
When the maximum applicable motor output > 300 kW, the drive uses 0.1 kW units.
•
The maximum applicable motor output changes when the value for
C6-01 [ND/HD Duty Selection]
changes.
◆
E3: V/F PARAMETER MOTOR 2
E3 parameters
set the control mode and V/f pattern used for motor 2.
Note:
V/f preset patterns equivalent to those set with
E1-03 [V/f Pattern Selection]
are not available for
E3 parameters
. Use
E3-04 [M2 Max
Out Frequency]
to
E3-10 [Min Output Voltage]
to manually set the V/f pattern.
■
Notes on Manually Setting V/f Patterns
Figure 12.68 Motor 2 V/f Pattern Diagram
•
To configure a linear V/f pattern at frequencies lower than
E3-06 [M2 Base Frequency]
, set
E3-07 = E3-09 [M2
Mid A Frequency = M2 Min Out Frequency]
. In this application, the drive ignores
E1-08 [Mid A Voltage]
.
•
Set the five frequencies as specified by these rules:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04 [M2 Min Out Frequency ≤ M2 Mid A Frequency < M2 Base
Frequency ≤ M2 Mid B Frequency ≤ M2 Max Out Frequency]
Incorrect settings will trigger
oPE10 [V/f Data Setting Error]
.
•
If
E3-11 = 0.0 Hz
, the drive will ignore the V/f pattern settings.
•
When you use
A1-03 [Init Parameters]
to initialize the drive, the drive will reset the manually set values for
E3-
04 to E3-13 [M2 Max Out Frequency to M2 Base Voltage]
to default values.
■
E3-01 M2 Control Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
E3-01
(0319)
M2 Control Method
Selection
Sets the control method for motor 2.
0
(0 - 3)
Note:
•
When you change this setting, the drive will set all parameters that are dependent on this parameter to their default settings.
•
Parameter
L1-01 [Motor Cool Type for OL1 Calc]
sets the protection operation of
oL1 [Motor Overload]
the same as Motor 1.
•
When you use parameter
A1-03 [Init Parameters]
to initialize the drive, this parameter is not reset.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...