SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
◆
d2: REFERENCE LIMITS
d2 parameters
set the upper and lower frequency limits to control the motor speed. Apply these parameters to for
example, run the motor at low-speed due to mechanical strength concerns, or if the motor should not be run at low
speed because of lubrication issues with the gears and bearings.
The upper frequency limit is set in
d2-01 [FRef Upper Limit]
and the lower limit is set in
d2-02 [FRef Lower
Limit]
.
Figure 12.55 Upper and Lower Frequency Limits
■
d2-01 FRef Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
d2-01
(0289)
FRef Upper Limit
Sets maximum limit for all frequency references. This value is a percentage of
E1-04 [Max
Output Frequency]
.
100.0%
(0.0 - 110.0%)
When the frequency reference is more than the value set in
d2-01
the drive will continue to operate at the value set
in
d2-01
.
■
d2-02 FRef Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
d2-02
(028A)
FRef Lower Limit
Sets minimum limit for all frequency references. This value is a percentage of
E1-04 [Max Output
Frequency]
.
0.0%
(0.0 - 110.0%)
When the frequency reference is less than the value set in
d2-02
, the drive will continue to operate at the value set
in
d2-02
. The motor will accelerate to the
d2-02
value after the drive receives a Run command and a lower
frequency reference than
d2-02
has been entered.
■
d2-03 Analog FRef Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
d2-03
(0293)
Analog FRef Lower Limit
Sets the lower limit of the master frequency reference (Multi-Step Speed 1) as a percentage of
E1-
04 [Max Output Frequency]
.
0.0%
(0.0 - 110.0%)
This parameter does not change the lower limit of Jog reference, frequency reference for multi-step speed
operation, or the auxiliary frequency reference.
The drive operates at the value set in
d2-03
when the frequency reference decreases to less than the value set in
d2-03
.
Note:
When lower limits are set to parameters
d2-02 [FRef Lower Limit]
and
d2-03
, the drive uses the larger value as the lower limit.
◆
d3: JUMP FREQUENCY
The Jump frequency is a function that sets the dead band to a specified frequency band. If a machine that operated
at constant speed is operated with variable speed, it can make resonance. To operate the machine without
resonance from the natural frequency of the machinery mechanical system, use a frequency band jump.
You can program the drive to have three different Jump frequencies. Set
d3-01 to d3-03 [Jump Frequency 1 to
Jump Frequency 3]
to the median value for the jumped frequency and set
d3-04 [Jump Frequency Width]
to the
Jump frequency width.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...