SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
239
■
Loopback Test
The loopback test uses function code 08 (Hex.) and returns the command message as a response message. This
test checks communication between the master and slave. The test code and data can use desired values.
The following figure shows examples of messages given out when the loopback test is done with the drive of
slave 1.
Figure 6.10 Message Example When Doing the Loopback Test
■
Writing to Multiple Holding Registers
You can write the data that you set to the number of holding registers set in function code 10 (hex). You must
configure the number of the holding registers and each 8 higher bits and 8 lower bits in order in the command
message for the write data. You can write to a maximum of 16 holding registers.
The following figure shows example messages when you use the PLC to set Forward run in the drive of slave 1
with a 60.00 Hz frequency reference.
Note:
The number of bytes set in the command message set the data quantity × 2 during the command message. The response message uses
the same formula.
Figure 6.11 Message Example When Writing to Multiple Holding Registers
When you rewrite the parameter value with the write command through the
H5-11 [Mbus ENTER Command
Mode]
setting, you must use the Enter command to save and enable the contents of the changes. Refer to
Mbus ENTER Command Mode on page 749
and
for more information.
■
Reading from More than One Holding Register/Reading the Indicated Register
The drive uses function code 5A (Hex.) to write to more than one register, then it reads the contents of four
holding registers at the same time.
The function for writing to more than one register is the same as the function for function code 10 (Hex.). You can
write to a maximum of 16 holding registers.
The four holding registers to be read from are specified in
H5-25 [Mbus 5A Reg1 Selection] to H5-28 [Mbus 5A
Reg4 Selection]
.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...