196
SIEPYEUOQ2A01G AC Drive Q2A Technical Manual
A - SW (ON)
B - Screw (OFF)
Figure 5.14 EMC Filter Switch Location (4453 - 4675)
If you lose an EMC filter switch screw, install the correct size screw with the correct tightening torque.
NOTICE:
Only use the screws specified in this manual. Failure to obey could damage the drive.
Table 5.7 Screw Sizes and Tightening Torques
Model
Screw Size
Tightening Torque
N
∙
m
2004 - 2082, 4002 - 4060
M4 × 20
1.0 - 1.3
2110 - 2211, 4075 - 4168
M4 × 25
1.0 - 1.3
2257 - 2415, 4208 - 4675
M5 × 25
2.0 - 2.5
■
Installing the External EMC Noise Filter
Drive models 2xxxA and 4xxxA must meet conditions in this section to comply with EN 61800-3:2004+A1:2012.
Connect an EMC noise filter to the input side (primary side) that complies with European standards as specified
by the manufacturer.
Use this procedure to install an EMC noise filter to make machinery and devices added to the drive comply with
the EMC Directive.
1.
Install the drive and EMC noise filter on the same grounded metal plate.
2.
Wire the drive and motor.
3.
Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft.) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 5.15 Wiring the Drive and Motor
Note:
• Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
• The maximum wiring length between the drive and motor is 10 m (32.8 ft.). Keep the cable between the drive and motor as
short as possible.
• Keep the grounding wire as short as possible.
4.
Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
Содержание Q2A
Страница 2: ...This Page Intentionally Blank 2 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 12: ...12 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 18: ...i 2 Legal Information 18 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 28: ...1 2 Features and Advantages of Control Methods 28 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 64: ...2 9 Installation Methods 64 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 166: ...4 9 Test Run Checklist 166 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 172: ...5 2 European Standards 172 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 173: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 173...
Страница 174: ...5 2 European Standards 174 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 175: ...Standards Compliance 5 5 2 European Standards SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 175...
Страница 176: ...5 2 European Standards 176 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 258: ...6 2 Modbus Communications 258 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 356: ...8 7 Storage Guidelines 356 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 357: ...SIEPYEUOQ2A01G AC Drive Q2A Technical Manual 357 9 Disposal 9 1 Safety Precautions 358 9 2 Disposal Instructions 359...
Страница 360: ...9 2 Disposal Instructions 360 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...
Страница 526: ...11 20 Parameters Changed by PM Motor Code Selection 526 SIEPYEUOQ2A01G AC Drive Q2A Technical Manual...