background image

16

17

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO L-G5.3/BF – Q CELLS

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO L-G5.3/BF – Q CELLS

17

16

0.20 in (5 mm)

in 

(0 

mm)

NA

Option 1:

 

Ä

Fasten the module with 4 clamps  in the specified 
clamping range, see Fig. 2, p. 8.

 

Ä

Tighten clamps according to manufacturer’s 
instructions.

 

Ä

Maintain an interval of at least 0.39 in (10 mm) 
between two modules along the short side and 
0.20 in (5 mm) along the long side.

NOTE! Module damage may occur!

 

Ä

Do not subject modules to mechanical tension. 
Max. torsion 0.12 in/ft (10 mm/m).

Option 2:

 

Ä

Install the module at the 4 mounting points,  
see Fig. 2, p. 8.

 

Ä

Tighten screws according to manufacturer’s 
instructions.

Option 3:

 

Ä

Install the module using mounting profiles,  
see Fig. 2, p. 8.

INSTALLATION

3.3  MODULE INSTALLATION

DANGER! 
Risk of fatal injury due to electric shock!

When disconnecting an electric circuit carrying direct current, 
electric arcs can occur that may result in life-threatening injuries.

 

Ä

Do NOT unplug the cable when under load.

 

Ä

Do NOT connect any exposed cable ends.

 

Ä

Electrical work may only be performed by qualified and skilled 
personnel (see page 3).

A solar module generates electrical current and voltage even 
at a low intensity of illumination. Sparks and electric arcs may 
result from the separation of a closed circuit. These can result 
in life-threatening injuries. The danger increases when several 
modules are connected in series.

 

Ä

Please be aware of that the entire open circuit voltage is active 
even at low levels of solar irradiation. 

 

Ä

Please follow the valid national regulations and safety guidelines 
for the installation of electrical devices and systems.

 

Ä

Please make sure to take all necessary safety precautions. With 
module or phase voltages of more than 120 V, the safety extra-
low voltage range is exceeded.

 

Ä

Carry out work on the inverter and the wiring with extreme 
caution.

 

Ä

Ensure that the modules are disconnected at the inverter prior 
to separation.

 

Ä

Be sure to observe the time intervals specified by the inverter 
manufacturer after switching off the inverter.

 

Ä

Make sure that the plugs can not be connected unintentionally.

 

Ä

Before working on the contacts, check them for safety extra-
low voltage.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Never open the junction box.

 

Ä

Do not remove bypass diodes.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Never touch live contacts with bare hands.

 

Ä

Cover connectors by suitable protective caps until 
installation.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Insulate any exposed cable ends.

 

Ä

Only connect cables with plugs.

DANGER! Risk of fatal injury due to electric shock! 

 

Ä

Only use dry, insulated tools for electrical work.

4  ELECTRICAL CONNECTION

4.1  SAFETY

Содержание Q.PEAK DUO L-G5.3/BF

Страница 1: ...Valid for North America INSTALLATION AND OPERATION MANUAL Q PEAK DUO L G5 3 BF solar modules...

Страница 2: ...operator are responsible for com pliance with all applicable statutory requirements and regulations The following regulations and standards must be upheld at all times during the installation operatio...

Страница 3: ...ulfillment of these requirements Other applicable documents This installation manual is only valid in combination with the following technical information DOCUMENT TYPE Product data sheet Packaging an...

Страница 4: ...with IEC 61215 and Design Load 1 5 in accordance with UL 1703 Installation using a mounting structure for solar modules Mounting Structure Requirements Requirements for the mounting structure Conform...

Страница 5: ...ubconstruction Mounting profile TYPE OF INSTALLATION POINT MOUNTING SYSTEM LINEAR MOUNTING SYSTEM INSTALLATION WITH CLAMPS HYBRID CLAMPING INSTALLATION ON MOUNTING POINTS 2 PLANNING 2 3 MOUNTING OPTIO...

Страница 6: ...system supplier The Q CELLS listed test load values were determinded with the following clamp parameters clamp width 1 58in 40mm and clamp depth 0 39in 10mm The system installer is responsible for the...

Страница 7: ...deter mining the maximum number of modules in the string Parallel Connection Modules may be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective insulation...

Страница 8: ...n NOTE Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 INSTALLATION 3 1 SAFETY AND TRANSPORT DANGER Risk o...

Страница 9: ...arcs may result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that the ent...

Страница 10: ...odules proceed in reverse order DANGER Risk of fatal injury due to electric shock Electrical work may only be performed by qualified and skilled personnel see page 3 Ensure correct polarity Use solar...

Страница 11: ...nt electrical shock or fire the frame of the module as well as any non current carrying metal parts of the system must be grounded While this section provides some information about grounding the Q CE...

Страница 12: ...Equipment Grounding Conductor Aluminum Frame Screw Stainless Steel Q CELLS solar modules are known for a long operating life and minimal maintenance effort and expense Dirt and grime are usually washe...

Страница 13: ...A 92618 USA TEL 1 949 748 59 69 EMAIL inquiry us q cells com WEB www q cells us Subject to change without notice Q CELLS Installation manual solar modules Q PEAK DUO L G5 3_BF_2020 08_Rev02_NA 24 INST...

Отзывы: