6.4
Reading Screen
The
Reading
screen displays the current volume of liquid remaining and liquid level over time.
Figure 10.
6.5
Settings Screen
The LSP-X01 Series sensor measures the hydrostatic pressure created by the liquid level in the tank. Con-
verting this measured pressure value to other parameters such as the tank level and the remaining liquid
volume in gallons requires the tank volume capacity, the tank maximum liquid height measured from the
bottom of the tank to the liquid surface when filled to the rated capacity, and the density of the liquid.
Measurements assume the tank has a uniform horizontal cross-section. To convert the measured pressure
to volumetric information, the LSP-X01 Series sensor requires the user to enter three parameters via the
uPyxis®
Mobile App’s
Setting
screen:
•
Tank Volume
(rated volume capacity of the tank)
•
Max Level Height
(from the bottom of the tank to the liquid surface when filled to the rated capacity)
•
Density
(of liquid in lb/gal)
From the
Settings
screen, you can also set the
Device Name
,
Display Unit
, and
Log Period
(time, in seconds,
between two measurements). To save your setting changes, press
Set Device
.
LSP-X01 Series User Manual
| +1 (866) 203-8397
9
Содержание LSP-X01 Series
Страница 1: ......