TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 9 of 30
PV7069-T 03/17
Part number 129209
CONFIGURE THE GATEWAY USING THE HTML INTERFACE:
This section will provide the parameters required for the TempTrac control. For more details of the gateway,
consult the gateway manual.
Connect your computer’s Ethernet port to the Ethernet port of the gateway.
Using a web browser, browse to the gateway at IP address:
192.168.1.24
default (If you have changed the
IP address, go to the appropriate address.).
If the device IP address has been changed and is not known, a utility is available from Feildserver.com.
Contact Fieldserver for more information.
Menu options vary depending on if you are configuring a LONWORKS gateway, BACNET Gateway set
for BACNET IP, a BACNET gateway set for BACNET MSTP, or a BACNET gateway set for MODBUS
TCP.
Using your browser, set the following and SUBMIT after each change.
MODBUS RTU Baud Rate:
9600
MODBUS RTU Parity:
NONE
MODBUS RTU Data Bits:
8
MODBUS RTU Stop Bits:
1
(BACNET options)
BACNET Network Number:
Must be unique network number on BACNET network
BACNET Node Offset:
This will be used to create the DEVICE INSTANCE. Sum the device
MODBUS Address and this number. Example 50000 Node MODBUS address 1 = 50001
Device Instance. Each MODBUS device will have its own Device Instance number.
(BACNET MSTP option)
BACNET MSTP Max Master:
127
(BACNET IP option)
BACNET IP Port:
47808 (Default)
BACNET COV:
COV Disable
(BACNET MSTP option)
BACNET BBMD:
- (Default
“-“, enabling this is an advanced feature, not recommended)
BACNET Router:
NO for 1 water heater, YES for multiple water heaters
SELECT THE DEVICE TYPE (BACNET & LONWORKS):
Press the
ADD
button, under
Node ID
enter the MODBUS address of the first heater. Typically you will
have the nearest heater setup as MODBUS address 1, and the next heater MODBUS address 2. All
heaters ship from factory with MODBUS Address set to 1. Each heater must have a unique MODBUS
address. (See previous section
Setup heater MODBUS address
)
Under
Current profile
, select the proper interface for the TempTrac control.
For BACNET Gateway:
Select
BAC_IP Temptrac
for BACNET IP
BAC_MSTP Temptrac
for BACNET MSTP
For LONWORKS Gateway:
Select
LON TempTrac Water Heater
Press the
Submit
button.
Add additional devices as required.
After adding all devices, restart the gateway by clicking the
SYSTEM RESTART
button.