TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 8 of 30
PV7069-T 03/17
Part number 129209
CONFIGURE GATEWAY DIP SWITCHES:
The ON position is toward the center of the module, and OFF is toward the edge of the module. Only the
BACNET gateway requires dip switch settings. The BACNET gateway is used for MODBUS TPC also.
DIP SWITCHES S0-3 PROTOCOL
Set Protocol (BACNET and MODBUS gateway only):
The gateway protocol is determined on power up by looking at
the “S” dip switches.
If the protocol is changed, the configuration/profiles must be
cleared and reconfigured. This is done with the HTML interface.
MODBUS RTU does not require a gateway.
LONWORKS: Configured in hardware, no need to adjust dip
switches.
DIP SWITCHES B0-4 BAUD
3PIN CONNECTOR TO BAS, Configure BAUD:
Default is 38400.
Configures the Baud rate for the 3 position terminal block.
This is the connection that will connect to the Building Automation
System (BAS).
This is used only when the protocol is BACNET MSTP.
A0-7 (BACNET MSTP) MAC ADDRESS:
Default is MAC address 3.
Configure the MAC address for
the BACNET Gateway by
summing the “A” dip switches
that are ON.
MAC address range: 1
– 127
Protocol
S0
S1
S2
S3
BACNET IP
OFF OFF OFF OFF
BACNET MSTP
ON
OFF OFF
OFF
MODBUS TCP
OFF
ON
OFF
OFF
MODBUS RTU
ON
ON
OFF
OFF
Baud
B0
B1
B2
B3
9600
ON
ON
ON
OFF
19200
OFF OFF OFF
ON
38400 *
ON
ON
OFF
ON
57600
OFF
OFF
ON
ON
76800
ON
OFF
ON
ON
1
2
4
8
16
32
64
<-sum for address
A0
A1
A2
A3
A4
A5
A6
A7
Address
OFF OFF OFF OFF OFF OFF OFF OFF 0
Invalid
ON
OFF OFF OFF OFF OFF OFF OFF 1
OFF
ON
OFF OFF OFF OFF OFF OFF 2
ON
ON
OFF OFF OFF OFF OFF OFF 3 *
Default
OFF OFF
ON
OFF OFF OFF OFF OFF 4
ON
OFF
ON
OFF OFF OFF OFF OFF 5
OFF
ON
ON
OFF OFF OFF OFF OFF 6
ON
ON
ON
OFF OFF OFF OFF OFF 7
OFF OFF OFF
ON
OFF OFF OFF OFF 8
ON
OFF OFF
ON
OFF OFF OFF OFF 9
OFF
ON
OFF
ON
OFF OFF OFF OFF 10
…
…
…
…
…
…
…
…
…
ON
ON
ON
ON
ON
ON
ON
OFF 127