TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 12 of 30
PV7069-T 03/17
Part number 129209
APPLICATION SPECIFICS:
Each product that uses the TempTrac control may have subtle differences. The following products address
the important information regarding each device.
Conquest 100 Gallon (199 – 299) & 130 gallon 399: (Smaller Conquest)
Model Numbers: 20 L 100A-GCL, 25 L 100A-GCL, 30 L 100A-GCL, 40 L 130A-GCL
Probe 1:
Is in the top of the tank, and controls the burner
Probe 2
: Is in the mid-section and controls the agitator pump using
Relay3
Probe 3
: Is in the flue
Alarm_AL2
: Alarm on any failure
Burner_Relay1
: Burner
Relay2
: Alarm dry contact
Relay3
: Agitator pump
Discrete connections:
External Enable:
Terminals R1
– R2, Jumper to enable. Heater ships with jumper on this. An external
enable/disable can be attached to this. This is a low current, low voltage contact. It is advised to use a
contact with gold plating. If not available, use 2 contacts in parallel.
Alarm
: A1 & A2 (Output from Heater) Closed = ALARM.
Remote Proving
: C1 & C2. Ships with factory jumper. Open will prevent burner from operating. Keeping
this open will create a lockout condition that will require user intervention.
Remote Equipment / Burner ON
: Contact that will close P1
– P2 during a heating cycle. Open, the heater
is not calling for heat.
No Setpoint Input
: There is not a discreet method to send a setpoint signal to the Conquest.
Conquest 130 Gallon (500 – 800): (Larger Modulating Conquest)
Model Numbers: 50 L 130A-GCML, 60 L 130A-GCML, 70 L 130A-GCML, 80 L 130A-GCML
Same as the smaller Conquest with the addition of modulation.
Modulation Rate
: Modulation rate, Low fire = 0, High Fire = 100
Discrete connections:
Same as the smaller Conquest with the following notes:
No Modulation Input
: There is not discreet way for a building automation system to control
the modulation (firing rate) of the Conquest.