background image

Dimensions are in inches unless otherwise noted. 
For standard and optional equipment, see form # PV 6811. 
* When connected with field provided 3” x 4” adapter of the same material as required for venting (see I&M). 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN 

 AND SPECIFICATION WITHOUT NOTICE.

 

STANDARD GAS PRESSURE REQUIREMENTS

 

  

VENTING REQUIREMENTS

 

MINIMUM FLOW GAS PRESSURE: 4.5" W.C.

 

MAXIMUM STATIC GAS PRESSURE:  10.5" W.C.

 

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

 

CONTACT YOUR PVI REPRESENTATIVE.

 

  

CATEGORY IV - POSITIVE PRESSURE, CONDENSING.

 

UL CLASSIFIED FOR SCHEDULE 40, SOLID-WALL PVC OR CPVC PIPE. 

“SANI” TEMPERATURE HEATER REQUIRES CPVC VENT PIPE 

 

 

 

 

SEE INSTALLATION MANUAL FOR VENTING 

AND DIRECT COMBUSTION AIR GUIDELINES.  

 

 

STANDARD ELECTRICAL REQUIREMENTS

 

  

120V, 1Ø, 60 HZ. 

MAXIMUM AMP DRAW (TRIAL FOR IGNITION): 6 

CONTINUOUS AMP DRAW WHEN FIRING: 1.3 

CONTINUOUS AMP DRAW DURING STANDBY: 0.03

 

  

PV 6812   09/08

 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

(800) 784-8326   

y

    www.pvi.com 

This product is protected by patents in  
the U.S., Canada and Mexico. 

MODEL NUMBER   

X

 

 

199 SS A-PN  

299 SS A-PN 

 

399 SS A-PN 

 

Input Btu/h 

199,000 299,000  399,000 

GPH Recovery Rate at 40°F to 140°F 

221 

340 

444 

Approximate Shipping Weight - lbs 

1000 

1100 

1100 

Flue Connection Diameter - inches 

3 * 

Hot Outlet and Cold Inlet - NPT 

1st Hour Delivery (100°F 

Δ

T) - gallons 

289 

397 

501 

Storage Capacity - gallons 

80 

70 

70 

PLATINUM

 ® 

• CONDENSING GAS WATER HEATER

 

STAINLESS STEEL TANK 

 

TANK SERIES 70 GALLONS 