Love 4C, 8C and 16C Microprocessor Based Temperature Process Control

 

Programming guide for PVI Industries EZ Plate Water Heater with Boiler Water Control Valve 

 
INITIAL SETTING MENU (all parameters in this menu must be set before programming other values) 

Press and hold the ENTER key for at least 3 seconds while at the Home Display in order to access the Initial Setting 
Menu. Pressing the INDEX key will cycle through the menu items. The parameter will be displayed in the top display, 
while its value will be displayed in the bottom display. The UP and DOWN arrows change the values of the parameters. 
The ENTER key must be pressed after any changes. 

 

INITIAL SETTING MENU

 

Parameter Description 

Value 

 

Input Selection. 

J2 

 

Temperature Units. 

 

Scale Height Limit. 

752.0 

 

Scale Low Limit. 

-4.0 

 

Control Mode. 

PID 

 

Heat/Cool Selection. 

HEAT 

 

Alarm 1 Setting. 

 

Alarm 2 Setting. 

 

Communications protocol language. 

ASCII 

 

Communications Write Function Feature. 

Off 

 

Controller Address: Set from 1 to 247. 

 

Baud Rate Setting. 

9600 

 

Communication Data Length. 

 

Communication Parity Bit. 

Even 

 

Communication Stop Bit. 

 

REGULATION MENU 

Press the ENTER key while at the Home Display in order to access the Regulation Menu. Pressing the INDEX key will 
cycle through the menu items. The parameter will be displayed in the top display, while its value will be displayed in the 
bottom display. The UP and DOWN arrows change the values of the parameters. The ENTER key must be pressed after 
any changes. 
 

REGULATION MENU

 

Parameter Description 

Value 

 

Auto Tune. 

Off 

 

Proportional Band Setting. 

 

Integral time (reset time). 

10 

 

Derivative time (rate time). 

 

Integral Deviation Offset Correction. 

 

Process Temperature Offset. 

0.0 

 

Analog Output High Limit. 

 

Analog Output Low Limit. 

 
OPERATION MENU 

Pressing the INDEX key will cycle through the below menu items. The parameter will be displayed in the top display, while 
its value will be displayed in the bottom display, except for the set point which is displayed in the bottom display on the 
Home Display. The UP and DOWN arrows change the values of the parameters. The ENTER key must be pressed after 
any changes. 
 

OPERATION MENU

 

Parameter Description 

Value 

 

Select Run - Stop Output Control. 

Run 

 

Set front panel security lock. 

Loc1 

 

Display the % output value for output 1. 

 
After Setting 

to Loc1, the control will no longer allow changes to the settings without following the unlocking procedures in the 

“Security Settings” of this guide.    See next page for reference information. 

 

 