SPECIFICATION FOR DOMESTIC WATER HEATERS 

Condensing, Gas-Fired Water Heaters with Nickel-Plated Storage Tanks 

 
 

Furnish and install the following 

POWER

 

VT

® gas water heater(s) as manufactured by PVI INDUSTRIES, INC of Fort 

Worth, Texas. 
 

 Model 

Btu/h 

 

GPH 

Recovery 

Storage 

Qty 

Number 

Input 

 

40° to _____°F   Tank 

 

 

___ ____________ 

__________ ________  _______ 

gallons

 

 

___ ____________ 

__________ ________  _______ 

gallons

 

 

___ ____________ 

__________ ________  _______ 

gallons

 

 

 

Efficiency 

 
 

The water heater will operate at a thermal efficiency of 94% when tested to ANSI Z21.10.3.  The water heater will 

comply with paragraph 7.2.4.4, the thermal efficiency and the standby loss requirements of  ASHRAE 90.1-1999. 

  

 
 

Pressure Vessel and Heating Surfaces 

 

 

The water heater will be a vertical fire tube design that is constructed and stamped in accordance with Section IV, 

Part HLW of the ASME code.  Both the storage and heating sections of the water heater will be National Board 
Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure. The fireside of 
the heating surfaces will be of boiler-grade steel. The waterside of the heating tubes will be sealed in copper.  The 
heating tubes will be rolled, beaded, and seal welded into the tube sheets.  The combustion side of the tube sheet will be 
insulated by a layer of ceramic fiber that will protect the tube sheet from both thermal stresses and failure that can result 
from the accumulation of scale and precipitants.   
 

Lining 

 
 

The tank will be a plated with electroless nickel (EN).  Plating will occur after the pressure vessel is completely 

fabricated and all welding is completed.  The EN plating will be a high-phosphorus (10%) and nonporous composition 
suitable for submersion service (ASTM B733 standard may be used as a guideline).  The finished lining will not require 
sacrificial anode rods.  For additional protection against galvanic corrosion, which may occur within the potable water 
system, the EN plating may have a high-dielectric-strength polymer overcoat.  

 
 

Burner and Venting 

 
 

Combustion will be provided by an induced-draft power burner that can operate with as little as 4-1/2 inches water 

column of gas pressure.  The water heater will be UL listed for use with plastic venting materials.  The heater will be 
capable of directly venting inlet air rated @ 120 equivalent feet and exhaust rated as follows: 4” vent - 50 equivalent feet 
on 1 MBtu/h model, 100 equivalent feet for other inputs; 6” vent – 390 equivalent feet on 1Mbtu/h model, 500 equivalent 
feet for other inputs. 

 

 

 

 

The burner will be equipped with a gas train meeting the specifications of: 

 
 

 

___ UL (standard equipment) 

___ FM   

___ IRI   

___ Other ______________________ 

 

 
 
 

(continued) 

 
 
 
 