Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6554 02/25/04
(800) 784-8326
•
www.pvi.com
LOW NO
x
TURBOPOWER
®
• PACKAGED WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
TANK SERIES 225 GALLONS VERTICAL
Recovery gph
c
Dimensions
(inches)
Blower
Motor
MODEL
NUMBER
40° - 120°F 40° - 140°F
INPUT
Btu/h
Min. Inlet
Flow Gas
Pressure
" W.C.
e
SCAQMD Energy
Model No.
A B C J
d
HP Amps
Shipping
Weight
lbs
250 P 225A-TPL
250
200
199,000
4.5
2TPL
199 MBtu/h
27
4
1/2
16
1/3
8
1230
375 P 225A-TPL
375
300
300,000
4.5
3TPL
299 MBtu/h
27
4
3/4
16
1/3
8
1240
500 P 225A-TPL
500
400
399,000
4.5
4TPL
399 MBtu/h
27
5
3/4
16
1/3
8
1250
c
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d
“J” dimension is for the burner housing only – gas train may exceed this dimension.
e
Standard gas train.
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV6550.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET GAS PRESSURE IS 14" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
STANDARD ELECTRICAL REQUIREMENTS:
CONTROL VOLTAGE:
120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
1/3 HP ARE 120V, 1Ø, 60 HZ.
208V, 230V AND 460V MOTORS ARE AVAILABLE BUT WILL
REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN
OPTIONAL CONTROL CIRCUIT TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.