background image

Содержание CO-RO3

Страница 1: ...APR2019 User Guide Food Service Reverse Osmosis Water Treatment System CO RO3 For correct operation installation it is essential to observe these instructions...

Страница 2: ...Pty Ltd 2019 What s Inside Safety Guides 3 The Food Service Reverse Osmosis System 3 Before Installation 4 Tools Materials Required 4 Location of System 5 Installation 6 Care Maintenance 8 Operating C...

Страница 3: ...hot or cold temperatures Temperature of the water supply to the reverse osmosis system must be between 4 C 40 F and 38 C 100 F Do not install on hot water lines All new membranes must be flushed for...

Страница 4: ...ressure etc Refer to the specifications to determine if your installation is within the limits A water quality analysis can be performed to determine if incoming water requires any treatment Contact y...

Страница 5: ...not exposed to freezing temperatures Do not expose unit or tubing to direct sunlight Water Supply To provide supply water to the RO system inlet a feed supply fitting is required or install pipe fitt...

Страница 6: ...n 1 5 Air Gap Required Above Flood Rim Inlet white Drain Tube black RO Assembly kg cm2 psi 15 200 150 100 50 0 10 5 0 AUTO SHUT OFF IN IN OUT OUT P O W E R Outlet Holding Tank Connection optional RO M...

Страница 7: ...Valve is in the OFF position 6 Rotate the Needle Valve in a counterclockwise motion until the valve is in full Bypass mode 7 Turn on the water supply slowly until the system has filled with water 8 R...

Страница 8: ...es of water per day should install external filters not supplied to reduce sediment chlorine and sediment larger than 10 microns Replacement of RO Membrane Elements The functional life of the RO membr...

Страница 9: ...m Operating Conditions Condition Minimum Maximum Inlet Pressure 300 kPa 875 kPa Inlet Temperature 4 C 38 C Inlet TDS 2 000 mg L Inlet Hardness 150 ppm Inlet Iron 0 mg L 0 1 mg L Inlet Manganese 0 mg L...

Страница 10: ...centrate water runs to drain continuously Plugged prefilter Plugged prefilter Replace plugged prefilter Consider sediment prefilter for non chlorinated applications Leak in product line Find and repai...

Страница 11: ...the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure Warranty New Zealand This warranty is given by Puretec Ltd Reg No 44643...

Страница 12: ......

Отзывы: