PureStorage FlashArray //X R2 Скачать руководство пользователя страница 1

FlashArray

Quick Installation Guide

Before You Begin

Recommended clearance for the front (cold aisle) is 91.5 cm
(36 in.). The minimum requirement is 81.5 cm (32 in.).

Recommended clearance for the rear (hot aisle) is 91.5 cm
(36 in.). The minimum requirement is 61 cm (24 in.).

No special clearance is required on top, bottom, or sides.

Recommended clearance for rack posts is 74 cm (29 in.) (the
default on most racks). Minimum is 61 cm (24 in.), Maximum
is 81.25 cm (32 in.).

Document Conventions

Symbol

Meaning

Potential for injury, physical damage, or loss of data
or array configuration information

Supplementary instruction

Best practice

For your information

Safety and Handling

Before you install the FlashArray, refer to

FlashArray

Safety and Compliance

.

Contacting Customer Support

For assistance, contact Pure Storage Support. You can
reach Support the following ways:

l

Visit

https://support.purestorage.com

l

Email

[email protected]

l

Call (800) 379-7873 in the U.S. For international sup-
port, see

https://support.purestorage.com

Support is available 24 hours a day, seven days a week.

Estimated Installation Time

You should be able to install the FlashArray in approximately
one hour and 15 minutes.

Preparing for Installation

The FlashArray chassis weighs 37.8 kg (83.2 lbs.),
DirectFlash Shelves weigh 39.8 kg (85.8 lbs.), and
expansion shelves weigh 20 kg (44 lbs.) each. Make
arrangements for safe lifting during installation.

Make sure you install DirectFlash Modules, Flash Mod-
ules, or blanks

after

rack mounting each chassis. The

FlashArray chassis with modules installed weighs
43.2 kg (95.2 lbs.).

Make sure that the rack can support the total weight of all
installed equipment including cables and rails (approx-
imately 48.5 kg or 107 lbs.), and that the total weight is
within the floor loading limit.

Have all necessary Fibre Channel and Ethernet cables
(not supplied by Pure Storage) available.

Verify that front and rear rack mounting posts are
between 61 and 91 cm (24-36 in.) apart, and that you
have 3 RU (13.3 cm or 5.25 in.) of vertical rack space for
the FlashArray chassis and 2 RU (8.9 cm or 3.5 in.) for
each expansion shelf.

Verify that the installation environment

l

Is within the operating temperature range of 5-35°C.

l

Does not have airflow ducts aimed directly at any
FlashArray chassis, controller, or shelf.

Have a local console (VGA monitor and USB keyboard
or a computer with terminal emulation capability) avail-
able in case it is required for software configuration or
diagnosis.

Make sure that cable lengths are adequate by mounting
the chassis and shelves in a contiguous stack as shown
in the DirectFlash Shelf, Expansion Shelf, and Add-on
Shelf Quick Installation Guides.

Before unpacking, inspect packages for shipping dam-
age. If damage is present, photograph it and contact
Pure Storage Technical Support before proceeding.

Save cartons and packing material in case return ship-
ment to Pure Storage is necessary.

Save all tools in FlashArray kit.

1. Unpack the FlashArray

Verify that the FlashArray package contains the items shown in Figure 1.

Figure 1. Unpacking the FlashArray

If storage shelves are included, refer to the

DirectFlash Shelf Quick Installation Guide

,

Expansion Shelf Quick Installation

Guide

, or

Add-on Shelf Quick Installation Guide

(in the "Open Me First" box) for the list of contents in the shelf package.

40-0154-01

Page 1 of 6

Содержание FlashArray //X R2

Страница 1: ...5 2 lbs Make sure that the rack can support the total weight of all installed equipment including cables and rails approx imately 48 5 kg or 107 lbs and that the total weight is within the floor loading limit Have all necessary Fibre Channel and Ethernet cables not supplied by Pure Storage available Verify that front and rear rack mounting posts are between 61 and 91 cm 24 36 in apart and that you...

Страница 2: ...the rear screws only Front screws are installed later 4 All rack types Secure the rear of each rail to the rack with the screws provided in the Accessory Kit One screw is provided for the rear of each rail Use the second or fifth hole up from the bottom of each rail shown going into the fifth hole on Figure 4 5 Repeat 1 4 above to install the second rail Make sure to install the rear of each rail ...

Страница 3: ... close the slam latches See Figure 7 Threaded hole racks only Secure the front of each rail to the rack with screws that fit the rack s threaded holes For example if the rack has 10 32 threads you can use the screws provided in the Accessory Kit If the rack has threads of another size you must obtain matching screws Figure 6 Mounted Chassis Figure 7 Securing Front of Rail 4 Install DirectFlash Mod...

Страница 4: ...AS card in the quad port mezzanine you can connect SAS0 through SAS3 to expansion shelves See the Expansion Shelf Quick Installation Guide for more information 5 After connecting pull gently on the cables until you feel resistance to ensure they are secure Repeat steps 1 5 for the second controller Figure 9 FlashArray Controller Ports QP ETH and FC PCIe Cards Shown 6 Unpack and Install Shelves Unp...

Страница 5: ...m the Accessory Kit to connect the CT0 KVM port see Figure 9 for the port location to a local console The KVM cable has one serial one VGA and two USB ports Use a VGA monitor and USB keyboard or a computer e g a laptop equipped with a serial to USB converter and terminal emulation software as a local console The terminal settings for the serial port are 8 N 1 8 data bits no parity 1 stop bit Xon X...

Страница 6: ...emarks or registered trademarks of Pure Storage Inc in the U S and other countries Other company product or service names may be trademarks or service marks of their respective owners The Pure Storage products described in this documentation are distributed under a license agreement restricting the use copying distribution and decom pilation reverse engineering of the products The Pure Storage pro...

Отзывы: