Disinfection Procedure

UV disinfection is a physical disinfection process and does not add any potentially harmful chemicals to the water. As UV 
does not provide a disinfection residual, it is imperative that the entire distribution system located after the UV be chemically 
disinfected to ensure that the water is free from any bacteriological contaminants. The disinfection process must be per-
formed immediately after the UV unit is installed and repeated thereafter whenever the UV is shut down for service, without 
power, or inoperative for any reason. The procedure for sanitizing the plumbing system is readily accomplished as follows:

1.   Shut off the upstream water supply that feeds water into the reactor chamber and depressurize water system. Remove 

the pre-filter cartridge and fill the sump with 1-2 cups of household (5.25%) bleach (chlorine) - Do NOT use hydrogen 
peroxide. At all times during the process, make sure the UV unit (and lamp) is turned on and operational!

2.   Repressurize water system, open each faucet and allow cold water to run until you smell chlorine, shut the faucet off and 

then repeat the process for each faucet, including hot water. You must ensure that all taps, including outside faucets, 
dishwashers, shower heads, washing machines, connections to refrigerators, toilets, etc., pass chlorinated water.

3.   Once all the locations have passed the chlorine disinfection solution, you will need to leave the solution sit for a period 

of 20 - 30 minutes. Reinstall the pre-filter cartridge into the filter and then flush the chlorine solution from the system until 
no chlorine smell is detectable. Make sure that each fixture that was disinfected in step 2 is completely flushed of the 
chlorine solution as the consumption of this water is not advised due to the extremely high concentration of chlorine. It is 
important to remember that in the event that a UV is briefly shut down for routine cleaning or during power interruptions 
where water could have passed through the system, the aforementioned procedure must also be followed.

  

Note A:

 The addition of chlorine (bleach) to a hot water tank that has in the past been fed with untreated raw water with 

high levels of other contaminants (iron, manganese, hydrogen sulphide, organics, etc.) will result in oxidation of these 
contaminants and may require repeated flushing of the hot water tank. This contingency must be dealt with indepen-
dently under the startup procedure for any other conditioners that may form a part of the pre-treatment for the UV unit.

 

 Note  B:

 The above procedure (Steps 1 to 3) will result in a massive chlorine residual far in excess of the 0.5 to 1.0 mg/L 

typically present in municipally chlorinated water and of a magnitude consistent with the minimum 50 mg/L chlorine 
solution recommended for the disinfection of distribution systems known to be contaminated. Do not consume water 
until complete system has been flushed.

Figure 1D

Drip Loop

Содержание Buv-12

Страница 1: ...UAL OWNER S GUIDE Stainless Steel Ultraviolet Water Purification System Buv 6 Buv 8 Buv 12 55003 0612 System Tested and Certified by NSF International against NSF ANSI Standard 55 for Disinfection Per...

Страница 2: ...bled and they are unable to reproduce Since the cell is now sterile or dead it is no longer a threat PURA Systems PURA recommends that all UV systems include pre filters to process the water before it...

Страница 3: ...nd warnings on the water disinfection system 10 If an extension cord is necessary a cord with a proper rating should be used A cord rated for less Amperes or Watts than the disinfection system rating...

Страница 4: ...that may be used for the installation Routine Maintenance It is important that any water treatment system be properly maintained to ensure consistent water quality The information provided on this pag...

Страница 5: ...I make sure that this is taken into consideration prior to any installation The system can either be installed vertically inlet port at the bottom Figure 1A or horizontally Figure 1B When selecting a...

Страница 6: ...ter from potentially entering the controller 5 Install the UV lamp and sleeve as outlined on pages 8 9 6 When all plumbing connections are made slowly turn on the water supply and check for leaks The...

Страница 7: ...the locations have passed the chlorine disinfection solution you will need to leave the solution sit for a period of 20 30 minutes Reinstall the pre filter cartridge into the filter and then flush the...

Страница 8: ...er being careful not to angle the lamp as it is removed from the chamber If the lamp is removed on an angle pressure will be applied on the inside of the quartz sleeve causing the sleeve to fracture S...

Страница 9: ...ction on page 8 9 Slowly turn on the water and pressurize the reactor to verify that there are no leaks 10 Reconnect to power source NOTE If the system is put on a temporary bypass or if it becomes co...

Страница 10: ...system 3 Heated Product Water A Common problem caused by infre quent use of water A Run water until it returns to ambient tempera ture 4 Water Appears Milky A Caused by air in the water lines A Run w...

Страница 11: ...ance Data Sheet While testing was performed under standard laboratory conditions actual performance may vary This Class B system or component conforms to NSF ANSI 55 for the supplemental bactericidal...

Страница 12: ...rranty shall be void ALL IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED IN DURATION TO THE PERIOD SPECIFIED ABOVE FOR PROD...

Отзывы: