Pump “Advanced” Parameters
The following parameters are used to set the “Advanced” Pump features.
Pump Run On
This feature is used to periodically allow the pumps to continue operating
below their normal “OFF” point, to discharge any sediment that may have
settled at the bottom of the vessel.
P349 Prime Level
Sets the required level to ensure pumps are fully primed after a pump run
on has occurred. Following a pump run on, any pump, whose “ON” point is
below the Prime Level will be held “OFF” until the Prime Level has been
exceeded.
P350 Run Interval
Set required time period, in hours, at which pump run on should occur.
P351 Run Duration
This parameter sets the length of time, in seconds, that pumps will run on
for, it should be noted that only one run on is allowed per Run Interval.
Starting
This feature is used to reduce the effects of power surges, caused by
switching of pumps, in the following instances, (
P352
)
Power
surge
(mains
or hydraulic) that is generated when multiple pumps are started
simultaneously, (
P353
)
Power
resumption
following a power failure.
P352 Start Delay
Set the required time period, in seconds, that should elapse between pumps
starting.
Default = 10 seconds.
P353 Power Delay
Set the required time period, in seconds, that should elapse before pumps
are allowed to start following a power failure.
Default = 10 seconds.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...