PULSAR MEASUREMENT
89
The
third parameter
has
no function
when
miscellaneous relay
is chosen
and will not be displayed.
The
fourth parameter
, and
fifth parameter
, are set to determine the switch
points, “
ON
” and “
OFF
” for the relay. See
miscellaneous
function table
(
P211, 221, 231, 241, 251, 261
) for further information.
P211, 221, 231, 241, 251, 261 = 1 (Clock)
P213, 223, 233, 243, 253, 263
–
Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at
which relay will energise. Default =
00:00
(
HH:MM
)
P214, 224, 234, 244, 254, 264
–
Relay Setpoint 2
Relay Setpoints are entered in seconds to set the
Time Period
that the relay
will remain ‘ON’.
Default = 0.00 mins.
P210, 220, 230= 2 (Totaliser)
P213, 223, 233, 243, 253, 263
–
Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on-board totaliser
(P820) should be multiplied by to provide a relay closure.
Default = 0.00
P214, 224, 234, 244, 254, 264
–
Relay Setpoint 2
Relay Setpoints are entered in seconds to set the
Time Period
that the relay
will remain ‘ON’.
Default = 0.00 secs.
Pump by Time
When a relay is assigned to Pump by Time the pump will come on (energise)
at its normal “
ON” level
setpoint, and de-energise at its
OFF level
setpoint
or after a predetermined
time
period,
whichever occurs first.
P210, 220, 230, 240, 250, 260 = 5 (Pump by Time)
When a relay is being used for a
pump by time
function, the
second
parameter
determines the
pump duty
that will be used to determine the
operating cycle.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...