mA Input
The
4-20 mA (Auxiliary) input
is available as an
option
(Consult Pulsar for
details of availability), and can be used to replace the transducer for
applications where an ultrasonic transducer cannot be used.
P119 mA Status
If P101 (Xducer) = 1 (Auxiliary)
This indicates the status of the Auxiliary input if selected
OPTION
DESCRIPTION
1 = mA OK (Default)
mA Input present and functioning correctly
1 = mA Open
No input (device) is being detected
2 = mA Short
Input is indicating a fault condition
P120 Low mA in
This parameter sets the current input figure that is used to represent empty
when using the optional current input, instead of an ultrasonic transducer.
Default = 4ma
P121 High mA in
This parameter sets the current input figure that is used to represent span
when using the optional current input, instead of an ultrasonic transducer.
Default= 20mA
P122 Low Level in.
This parameter sets the distance to empty point when using the optional
current input, (Aux. input) instead of an ultrasonic transducer.
P123 High Level in
This parameter sets the distance that is full (span) when using the optional
current input, (Aux. input) instead of an ultrasonic transducer.
P124 Low mA Trim
This parameter allows you to “calibrate” the
Zenith to the
Low mA Input
from the device being used. If the expected low value, from the device
connected to the mA Input, is not displayed, then you can trim it using this
parameter.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...