Example 2 Sump Control (pump down)
A sump is typically used to temporarily hold water or effluent, and when the
level reaches a specific point, the sump is pumped down, with the fluid
being transferred to another process.
In this example, there are two pumps, which will be set to
alternate duty
assist
, so they come on alternately. Pump 1 is to be set to relay 1, pump 2 to
relay 2, and the high-level alarm to relay 3.
This will operate as follows. During normal operation,
pump 1
will come on
at 0.84m and pump down to 0.56m. The setpoints are then shifted to
pump
2
, which will come on first next time. During peak periods, when
pump 1
cannot cope,
pump 1
will come on at 0.84m,
pump 2
will come on at 1.4m,
and pump down to 0.56m. The setpoints are then shifted to
pump 2
, which
will come on
first next time
.
If neither pump can cope, and the level rises to 2.38m, then the alarm relay
(relay 3) will come on and go off when the level falls to 2.24m. This will
indicate insufficient capacity of the pumps. The display will show the level in
the sump and the mA output will be representative of level where 4mA =
empty level (0%) and 20mA = 2.8m (100%).
Empty Distance (P105), 3.5m
100%. Span (P106), 2.8m
85%. High alarm on (P233), 2.38m
80%. High alarm off (P234), 2.24m
0%, Empty level
20%. Pump 1+2 off (P214, 224), 0.56m
30%. Pump 1 on (P213), 0.56m
50%. Pump 2 on (P223), 1.4m
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...