Example 1 Level Monitoring with Alarms
A vessel, containing liquid that has a variation in level that is to be
monitored, with a high-level alarm set on Relay 1 and low-level alarm set on
Relay 2.
In this example, when the level rises to 2.38 m, relay 1 will come on until the
level drops to 2.24 m when it will turn off. If the level drops to 0.28 m, then
relay 2 will come on until it rises 0.42 m when it will turn off.
The display will show the level in the tank.
The mA output will be representative of level where 4mA = empty level (0%)
and 20mA = 2.8m (100%).
Empty Distance (P105), 3.5m
100%. Span (P106), 2.8m
85%. High alarm on (P213), 2.38m
80%. High alarm off (P214), 2.24m
0%, Empty level
10%. Low alarm on (P223), 0.28m
15%, Low alarm off (P224), 0.42m