PULSAR MEASUREMENT
155
Test Parameters
Simulation
P980 Simulate
Test mode is used to simulate the application and confirm that all
parameters and relay setpoints have been entered as expected. During
simulation, there is a choice of whether the relays will change state (hard
simulation) or not (soft simulation), but the LED’s will always change colour
as programmed, and the current output will change. If you want to test the
logic of the system that the relays are connected to then select a hard
simulation, but if you do not want to change the relay state, then select a
soft simulation.
There are two simulation modes,
automatic
and
manual
. Automatic
simulation will move the level up and down between empty level or the pre-
determined
Start Level (P983)
and Pump/Control relay switch points, if you
wish to change the direction of the level movement e.g. to go beyond relay
setpoints, this can be done by using the arrow keys. In manual simulation,
using the arrow keys will allow you to move the level up and down as
required.
The choices for you to enter are as follows.
1= Manual soft simulation
2= Automatic soft simulation
3= Manual hard simulation
4= Automatic hard simulation
Whilst in Automatic hard simulation (
P980 = 4
) the switching of digital
inputs can be simulated by pressing the corresponding numeric key to the
input to be switched, each time the numeric key is pressed it will toggle the
input between On and Off.
To return to program mode, press
‘
CANCEL
’
and test mode will end.
Important Notice
Pump start delay (which by default is 10 seconds) is set to 0 during
simulation.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...