Float Switch (FS) Backup
About Float Switch Backup
This digital feature is used with a float switch, where it can be used alongside
a transducer or as a backup method for when a transducer goes into failsafe.
The high input will have a timer and a level set point, which will allow for the
unit to power on every pump below the set point for the specified amount
of time as set in
P332 Pump Run Time
.
The low input will simply switch off all the pumps that have been set on the
controller.
Common Par
P330 Mode of Operation
OPTIONS
DESCRIPTION
0 = Off (Default)
Float Switch Backup is not used
1 = Always
Backup will be active continuously and will always
respond to an input from a Backup device, always.
2 = On Xdr Fail
Backup will only be active at times when the unit
has gone into a Failsafe mode.
P330 Input Filter
This parameter can be used to ignore spurious changes of state on the
digital inputs and determines the time that a change of state must be
present before it is recognised as a valid input.
Enter a value in seconds: Min = 1 (
Default
), Max = 999.
P330 Pump Run Time
This parameter tells the unit to switch the pumps off after the specified
amount of time, if the level of the float switch has not been reached.
Enter a value in minutes: Min = 0.1 (
Default
), Max = 9999.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...