Display Parameters
P1 and P2
Options
P*800 Display Units
This parameter determines whether the reading displayed is in
Measurement Units
(
P*104
), or as a
percentage
of
span.
OPTION
DESCRIPTION
1 = Measured (Default)
Display is in
selected unit’s dependent in Mode (
P100
)
2 = Percentage
Display is in
percentage
of span dependent in Mode
(
P100
)
P*801 Decimal Places
This parameter determines the number of decimal places on the reading
during run mode. Minimum = 0 (No decimal places), Maximum 3 = (3
decimal Places).
Default = 2
(2 decimal Places).
P*802 Display Offset
The value of this parameter is added to the reading before it is displayed, in
Measurement Units
(
P*104
). It does not affect the relay setpoints or the
mA output, only the reading on the display.
You could use this feature if for example you wanted to reference the
reading to sea level, where you would enter the distance between
Empty
Level
(
P*105
) and sea level. If the empty level point is below sea level, then
enter a negative value.
P*804 Display Conversion
The reading is multiplied by the value of this parameter before being
displayed. The default is 1.0, but if for example you wanted to display the
reading in yards, then set the
Measurement Units
(
P*104
) to feet and set
P*804
to 3.