background image

 

PSBSOF 10A12 

 

v.1.0 

 

PSBSOF 13,8V/10A/OF 

 

Enclosed switch mode buffer power supply 

 

with technical outputs. 

 

EN** 

 

Edition: 3 from 01.06.2016

 

Supercedes edition: 2 from 11.05.2015

 

 

 

  
                       

 
 
 

 
 

 

 
 

 
 

              

 

 

 
 
 
 

 
 
 

 

 

     

 

 

 

Содержание PSBSOF 10A12

Страница 1: ...PSBSOF 10A12 v 1 0 PSBSOF 13 8V 10A OF Enclosed switch mode buffer power supply with technical outputs EN Edition 3 from 01 06 2016 Supercedes edition 2 from 11 05 2015 ...

Страница 2: ...ock diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operation indication 3 1 Optical indication LEDs on the PCB of the PSU 3 2 Optical indication with an additional module 3 3 Technical outputs OC type 3 4 Relay technical outputs Relay technical outputs 4 Service and operation 4 1 Overload or sh...

Страница 3: ...ualization available at www pulsar pl 1 Buffer power supply PSBSOF 13 8V relay module MPSBS PSBSOF 10A12 MPSBS 2 Buffer power supply PSBSOF 13 8V 8x1A relay module MPSBS PSBSOF 10A12 LB8 8x1A AWZ579 or AWZ580 MPSBS 1 2 Block diagram Fig 1 Fig 1 Block diagram of the PSU ...

Страница 4: ...s AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure indication hi Z state failure 0V state PSU status O K LoB technical output of low battery voltage indication hi Z state battery voltage UBAT 11 5V 0V state battery O K BAT terminals for battery connection AUX DC power output AUX U AUX GND Des...

Страница 5: ... connector Battery connectors positive BAT red negative BAT black Optical indication module PKAZ108 version Fig 3 The view of the PSU 1 4 Technical parameters Electrical parameters Table 3 Mechanical parameters Table 4 Safety of use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 1 1A 230V A...

Страница 6: ...f yellow battery charging permanently illuminated fully charged off Technical outputs EPS output indicating AC power failure PSU output indicating no DC power PSU failure LoB output indicating low battery voltage OC type 50mA max Normal operation L state 0V failure hi Z state delay time 10s 60s 20 jumper selectable TAC OC type 50mA max Normal operation L state 0V failure hi Z state OC type 50mA ma...

Страница 7: ... by assigning an appropriate fuse in the fuse box The electrical system shall be made in accordance with applicable standards and regulations The power supply shall be mounted in a close casing a cubicle a terminal device and in order to fulfill LVD and EMC requirements the rules for power supply encasing and shielding shall be observed according to application 2 2 Installation procedure 1 Before ...

Страница 8: ...section 1 1 12 Mount the additional optical indication plate and connect to the socket on the PCB of the power supply using a cable Fig 2 pt 7 13 Close the cover after installing and checking the operation of the power supply 3 Power supply operation indication 3 1 Power supply operation indication Additionally the PSU is fitted with LED lights indicating the operating status AC LB and AUX at the ...

Страница 9: ...ower supply technical outputs are open collector OC type as shown schematically below Fig 4 Electrical diagram of the OC technical outputs 3 4 Relay technical outputs If the OC type outputs are not sufficient to control the unit it is possible to use the MPSBS relay module changing technical outputs of the OC type to relay type Fig 5 The diagram of connecting the MPSBS module 4 Service and operati...

Страница 10: ...elow 10V 0 5V during battery assisted operation the batteries will be disconnected The battery protection is on when the PBAT jumper is off Caution It is not recommended to disable UVP since deep discharge of the batteries reduces their ability to store energy their capacity and lifetime 4 4 Maintenance All maintenance procedures can be performed after disconnecting the power supply from the power...

Страница 11: ...the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warrant...

Страница 12: ...www pulsar pl PSBSOF10A12 12 Pulsar Siedlec 150 32 744 Łapczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl ...

Отзывы: