Page 35
Ultimate Controller Fascia and Wall Mount setup
1.
Install and connect your Ultimate Controller as outlined in the Ultimate
Controller user manual.
2.
Prior to installing and connecting your
MicroFlow
sensor to the Ultimate,
you will need to set the sensors unique Modbus address by using
MicroFlow PC
. This is done by changing the Modbus ID value, which
can be done by the Modbus ID box in the software, or using the manual
parameter box and change P52 to between 2 & 125 (Ensure multiple
sensors have different addresses). For further details on changing
parameters and using
MicroFlow PC
, please refer to
Chapter 6 -
MicroFlow PC
where details of how to use the software is explained.
3.
Once a Modbus address is set, install and connect your
MicroFlow
sensor
to the Ultimate Controller as shown in
Chapter 2 – Installation –
Ultimate Controller (Fascia
&
Wall Mount)
of this manual.
4.
Power up the unit and enter program mode by pressing ‘Menu’ and
keying in ‘
1997
’ and pressing Enter to begin setting up the unit for
measurement.
5.
Select
Advanced Config.
>
Live List
, where the controller will now
search for the Modbus ID of the
MicroFlow
unit(s) that have been
connected.
6.
In
Advanced Config.
>
Modules
, Select the amount of
MicroFlow
sensors and press the ‘<’ button so that they appear in the ‘
Added
’
column. Now select each MFL (
MicroFlow
) and select ‘
Edit
’ to change
the Modbus ID to what has already been set and discovered in the
Live
List
. The controller will now reboot.
7.
Re-enter program mode by pressing ‘Menu’ and keying in ‘
1997
’.
8.
Select ‘
Setup
>
Application
>
Operation
’ and press the ‘+’ button to
add a point of measurement, which you can rename to something of your
choice.
9.
Select ‘
Velocity
’ where you will now be able to select the
MicroFlow
as
a velocity measurement point.
10.
Select ‘
Single
’ when only using one sensor to obtain velocity
measurements.
11.
If more than one sensor is to be setup for different channels, then repeat
‘
step 8
and
9’
in these instructions. If multiple sensors are to be used on
one channel, please select the appropriate sensors from the list on screen.
You can now select ‘
Avg, Diff, or Sum
’
as a mode of operation.
12.
If no further changes are needed, you can exit the screen and save your
changes.
Содержание MICROFLOW
Страница 1: ...MICROFLOW INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 6: ...58 59...
Страница 12: ...Page 6 EU Declaration of Conformity...
Страница 31: ...Page 25 Distance Distance Diagram 4 Diagram 3 Distance Distance Distance...
Страница 36: ...Page 30 This page is left blank intentionally...
Страница 44: ...Page 38 This page is left blank intentionally...
Страница 56: ...Page 50 This page is left blank intentionally...