background image

 

 

5

 

1.4 Specifications 
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 

      

Electrical parameters

 (tab. 3) 

Mains supply 

176÷264V AC 

Current up to 

0,45A@230VAC 

Power frequency 

50÷60Hz  

Supply power 

35W max.  

Efficiency 

74% 

Output voltage 

13,8V DC – buffer operation 
9,5V÷13,8V DC – battery-powered operation 

Output current 

2,0 A + 0,5A battery charge 

Output current t

AMB

<30°C 

2,0 A + 0,5A battery charge - refer to chart  1 

Output current t

AMB

=40°C 

1,4 A + 0,5A battery charge - refer to chart  1 

Voltage adjustment range 

12÷14VDC 

Ripple 

120mV p-p max. 

Battery charge current 

0,5A max. @ 7Ah (± 5%) 

Short-circuit protection SCP 

electronic 

Overload protection OLP 

PTC polymer fuse 

Overvoltage protection OVP 

U>115% ÷ 150% of the output voltage (set), power 
cut off, automatic return 

Excessive discharge protection UVP 

U<9,5 V (± 5%) – disconnection of battery terminal 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 

 
- red, normal status – on, failure: off 
- green, normal status – on, failure: off  

Technical outputs: 
- TAMPER indicates enclosure opening 

 
- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

 
 
Mechanical parameters (tab. 4) 

Enclosure dimensions 

285 x 297 x 80+8  (280 x 292 x 80) (WxHxD)

 

Fixation 

See figure 2 

Fitting battery 

17Ah/12V (SLA) max. 

Net/gross weight 

2,10kg / 2,20kg

 

Enclosure colour 

RAL 9003 

Closing 

Cheese screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power-supply: 

Φ

0,63-2,50 (AWG 22-10) 

Outputs: 

Φ

0,63-2,50 (AWG 22-10) 

Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not touch the assembly surface so that cables can be led 

     Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
500  V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

Содержание HPSB 2512C

Страница 1: ...HPSB 2512C v 1 0 HPSB 13 8V 2A 17Ah Buffer switch mode power supply unit EN Edition 1 st from 03 th of October 2011 Supercedes the edition ...

Страница 2: ...sed voltage of 12 V DC 15 The PSU provides voltage of U 13 8 V DC with output current of I 2A 0 5A for battery charging In case of power decay a battery back up is activated immediately The PSU is constructed based on the switch mode PSU with high energy efficiency The PSU is housed in a metal enclosure colour RAL 9003 which can accommodate a 17Ah 12V battery A micro switch indicates door opening ...

Страница 3: ...ates AC power 4 P1 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact sabotage protection NC 7 Additional connector for LED indication Tab 1 The elements of the power supply Part no Fig 2 Description L N L N power supply connector PE PE Protection connector electric shock protection V V DC supply output DC supply output GND Tab 2 Output terminals o...

Страница 4: ...4 Fig 2 The view of the power PSU ...

Страница 5: ...ode indicating DC power status at the PSU output red normal status on failure off green normal status on failure off Technical outputs TAMPER indicates enclosure opening microswitch NC contacts enclosure closed 0 5A 50V DC max Mechanical parameters tab 4 Enclosure dimensions 285 x 297 x 80 8 280 x 292 x 80 WxHxD Fixation See figure 2 Fitting battery 17Ah 12V SLA max Net gross weight 2 10kg 2 20kg ...

Страница 6: ...onal air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance During normal operation the total current drawn by the device may not exceed I 2A Maximum battery charge current 0 5 A Total device current battery 2 5 A max As the PSU is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection sha...

Страница 7: ... DC 9 After installing and checking proper working the enclosure can be closed 3 Operating status indication 3 1 LED indication of operating status The is equipped with two diodes on the front panel 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage ta...

Страница 8: ...rranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 8 All the services rendered by for...

Отзывы: