Page 9 

Terminal Connections 

Power 

The 

Flow  Monitor

  can  be  powered  from  mains  AC  or  from  a  DC 

source/battery  and  where  a  backup  DC  power  source  is  connected  it  will 
automatically  take  over  in  the  event  of  AC  power  failure;  DC  will 
automatically power the unit. When AC returns it will switch back.  

FlowPulse Sensor 

The FlowPulse sensor should be installed and connected, in accordance with 
the FlowPulse manual. 

Wire the FlowPulse sensor to the 

Flow Monitor 

sensor terminals, as on the 

previous page. 

Relay Outputs 

The  two  relays  can  be  programmed  to  a  variety  of  alarm  &  control 
functions.  The  relay  contacts  are  all  rated  at  2A  at  240V  AC.  All 
connections  should  be  such  that  the  short  circuit  capacity  of  the  circuit  to 
which  they  are  connected,  is  limited  by  fuses  rated  so  that  they  do  not 
exceed the relay rating. 

Current Output 

This  is  an  isolated  active  mA  output  of  4  -  20mA  or  0  -  20mA,  with  an 
option of a passive mA output. The load should not exceed 1K

RS485 termination switch 

By default, this is switched off, to enable RS485 termination both switches 
need to be switched to the ON position. 
 

 

 

 

 

 

 

 

Important Information 

If the equipment is installed or used in a manner not specified in this manual, 
then the protection provided by the equipment may be impaired. 

 

Содержание Flow Monitor

Страница 1: ...Flow Monitor INSTRUCTION MANUAL...

Страница 2: ......

Страница 3: ...Limited cannot be held liable for any errors Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserves the right to amend technical details as necessar...

Страница 4: ......

Страница 5: ...de 15 LED s 15 Program Mode 16 How to Access Program Mode 16 Test Mode 18 Using the RS232 Serial Interface 19 Parameter Defaults 19 Factory Defaults 19 21 Menu System Diagrams 21 Top Level Menu 21 App...

Страница 6: ...im 43 Failsafe 43 Totaliser Parameters 44 Setup 44 Totalisers 45 Tot Audit 45 System Parameters 46 Passcode 46 System Information 46 Date Time 47 Daylight Saving Time 47 Test Parameters 51 Simulation...

Страница 7: ...al will ensure that your installation is as simple as possible About this Manual It is important that this manual is referred to for correct installation and operation There are various parts of the m...

Страница 8: ...the product is ideally suited to applications where velocity monitoring reporting or control is required The controller is very easy to use and may be quickly and simply setup via the on board keypad...

Страница 9: ...ed active output passive output optional of 4 20 mA or 0 20 mA into 1K user programmable and adjustable 0 1 resolution Display 2 x 12 alpha numeric Serial Port RS232 for programming and data extractio...

Страница 10: ...Page 4 EU Declaration of Conformity...

Страница 11: ...osure bear in mind the following Easy access to the enclosure is maintained The mounting surface is vibration free The ambient temperature is between 20 C and 50 C There should be no high voltage cabl...

Страница 12: ...onitor should be mounted by drilling four holes suitable for size 8 screws length and type to suit your application And fix all four screws by removing the top cover to access the pre moulded mounting...

Страница 13: ...m cables fitted to the base of the Flow Monitor enclosure Important Information All cable glands should be tightened to the manufacturer s specifications The terminal compartment cover screws should b...

Страница 14: ...S485 Screen is connected to terminal 21 not shown on the above diagram Terminal Name Flow Monitor Terminal FlowPulse Terminal 0V GND 22 1 24V DC 23 2 RS485 SCR 26 8 RS485 24 9 RS485 25 10 Cable Screen...

Страница 15: ...an be programmed to a variety of alarm control functions The relay contacts are all rated at 2A at 240V AC All connections should be such that the short circuit capacity of the circuit to which they a...

Страница 16: ...5 mm of insulation from the end of each conductor Twist all exposed strands of the conductor together Insert the stripped conductor into the terminal block as far as it will go and tighten the termin...

Страница 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...

Страница 18: ...e display is used to monitor the simulated flow or velocity and mA output 1 Main Display 12 digit alpha numeric display Run Mode current measurement displayed dependent on measurement unit s chosen an...

Страница 19: ...the functions are shown below Hot Key Run Mode Program Mode System totaliser and resettable totaliser Not used with Flow Monitor Confidence level and signal strength Not used with Flow Monitor Not us...

Страница 20: ...r velocity moving up and down 1 Used to confirm each action for example select a menu option or when entering a parameter number or value 2 Used to confirm questions asked by your Flow Monitor such as...

Страница 21: ...by default are switched off and once the FlowPulse is initialised the display will show the current flow or velocity and the measurement unit After programming is complete any relays that are set will...

Страница 22: ...owed by the ENTER key The default passcode is 1997 so you would press the following Note There is a time out period of 15 minutes when in program mode after which time run mode will be resumed if you...

Страница 23: ...to run mode This is done by pressing ENTER at the display prompt Directly Editing Parameters If you already know the number of the parameter that you wish to look at or edit simply type the number in...

Страница 24: ...ram mode Then using the menu system select menu item Test then sub menu item Simulation Simply change the value of the parameter P980 to one of the following 1 Manual soft simulation 2 Automatic soft...

Страница 25: ...ing the unit on a new application before proceeding to program the unit for its intended application it is recommended that you ensure that all parameters are at their default values by completing a F...

Страница 26: ...Page 20 This page left blank intentionally...

Страница 27: ...ur Flow Monitor in the order they appear in the menu system Menu System Diagrams Shown below is a set of charts to show you how all the various parts can be found using the menu system Top Level Menu...

Страница 28: ...10 Pipe ID P111 Noise Adapt P113 Step Resp P104 Damping P115 Step Thresh P141 Protocol P143 Device Baud P144 Parity P145 Stop Bits P146 Format P147 Tx Delay P148 Poll Int P142 Device Addr Operation De...

Страница 29: ...y 2 P210 R1 Type P220 R2 Type P211 R1 Function P212 R1 I D P213 R1 Setpoint 1 P214 R1 Setpoint 2 P217 R1 Closures P218 R1 Failsafe P221 R2 Function P222 R2 I D P223 R2 Setpoint 1 P224 R2 Setpoint 2 P2...

Страница 30: ...isplay Menu Options P800 Display Source Failsafe P808 Fail Mode P809 Fail Time P801 Dec Places P803 Volume Unit P802 Meas Unit P804 Time Unit P805 Display Offset P806 Displ Converter Auxiliary P815 Au...

Страница 31: ...High Value Limits P836 Low Limit P837 High Limit Trim P838 Low Trim P839 High Trim Operation P831 mA Mode Setup P822 Tot Enable Totaliser P820 System Tot Tot Audit P460 Tot Date 1 P823 Tot Decimal P8...

Страница 32: ...le P971 DST Difference Pass Code P921 Enable Code P922 Passcode Sys Info Date Time Daylight Save P928 Serial No P929 Site Ident P930 Factory Def P933 Date Format P972 DST Start Time P973 Start Day P97...

Страница 33: ...Page 27 Test Menu Simulation P980 Simulate P981 Increment P982 Rate Hardware P991 Hard Test P992 mA Out Test P993 Relay Test P983 Test Max P984 Test Min...

Страница 34: ...lue of the damping sets the amount of flow readings it uses to create an average flow The default is set to 24 meaning the average of 24 readings will be used as the flow value Default 24 P105 Averagi...

Страница 35: ...required for the normal damping to be bypassed The range of the step response threshold is Min 22 Max 426 Default 60 426 relates to the Flow High value The higher the step response threshold the large...

Страница 36: ...n can be applied Min 20 Max 2000 Default 400 P134 Particle Density This parameter is used to set the type of material being measured in the pipe that the FlowPulse is attached to Option Description 0...

Страница 37: ...cted to Default 126 P143 Device Baud This parameter determines the baud rate that the processor uses to communicate with the FlowPulse sensor Default 19200 baud P144 Parity This parameter determines t...

Страница 38: ...Signed integer data 2 Float Motorola Format Motorola floating point format 3 Float IEEE Format IEEE 754 floating point format P147 Tx Delay This parameter determines the transmission delay that the p...

Страница 39: ...lay 1 210 to 218 Relay 2 220 to 228 Relay Type P210 P220 Relay Type This parameter defines what type each relay should be see the table below or available options Option Description 0 Not In Use Defau...

Страница 40: ...ity alarm P212 222 and two setpoints must be set P213 223 P214 224 3 Loss of Echo Alarm is raised if the Failsafe Timer P809 expires No setpoints are required 4 Loss of Clock Alarm is raised if the re...

Страница 41: ...fier 4 Low Relay goes ON when the value lowers to the ON setpoint and goes OFF when the value rises to the OFF setpoint ON OFF Relay Setpoints P213 223 and P214 224 Setpoints can be set in any order a...

Страница 42: ...s of Clock This parameter has no function and will not be displayed When P211 P221 1 or 2 P213 P223 Relay Setpoint 1 Determines the ON or OFF point for the alarm according to the ID selected P214 P224...

Страница 43: ...s OFF de energises as set in Relay Setpoint 2 P214 224 Important Information A control relay is started and stopped at the ON and OFF setpoints To control down reduce level then set ON higher than OFF...

Страница 44: ...relay pulse Default 0 00 secs Common Parameters P217 P227 Relay Closures This parameter displays the number of times the relay has activated since the relay has been in use It can be reset with any v...

Страница 45: ...urement Unit This parameter determines the measurement units showed on the reading during run mode Option Description 1 metres Default Measurement in metres 2 cm Measurement in centimetres 3 mm Measur...

Страница 46: ...lt 1 0 Failsafe P808 Fail safe Mode By default if a fail safe condition occurs then the display and the output are held at their last known values until a valid reading is obtained If required you can...

Страница 47: ...lay flow reading 2 Velocity Display velocity reading 3 Totaliser Display resettable totaliser mA Output Parameters Range P830 Output Range This parameter determines the range of the mA output from the...

Страница 48: ...uld be set to 0 00 m s and P835 High Setpoint should be set to 5 m s P834 Output Low Level This parameter sets the measurement value at which the low mA output will occur 0 or 4mA dependant on P830 Ou...

Страница 49: ...until you get the expected result on the device that is connected Failsafe P840 Output Fail safe Mode This parameter determines what happens to the output in the event of the unit going into fail safe...

Страница 50: ...ll state Units are L 1000 and the totaliser will be incremented every 1000 litres Option Description 1 1 1000 Totaliser will increment every 1 1000th units of flow 2 1 100 Totaliser will increment eve...

Страница 51: ...e Totaliser Displays the current value of the resettable totaliser This totaliser can be allocated to appear during run mode on the auxiliary display line P815 or alternatively via the Totaliser hot k...

Страница 52: ...current software revision P927 Hardware Revision This parameter will show details of the current hardware revision P928 Serial Number This parameter will show the serial number of the unit P929 Site...

Страница 53: ...Y MM DD The default is DD MM YY Daylight Saving Time P970 DST Enable When Enabled set to 1 the internal clock will be automatically adjusted to compensate for the difference between standard time and...

Страница 54: ...Sunday Default DST will start on a Sunday P974 Start Week This parameter will determine the week of the month P975 in which Daylight Saving Time is to start Option Description 1 Week 1 DST will start...

Страница 55: ...tart during the month of September 10 October DST will start during the month of October 11 November DST will start during the month of November 12 December DST will start during the month of December...

Страница 56: ...P979 End Month This parameter is used to select the month in which Daylight Saving Time is to end Option Description 1 January DST will end during the month of January 2 February DST will end during t...

Страница 57: ...ammed setpoints if you wish to change the direction of the velocity movement at any time this can be done by using the arrow keys In manual simulation using the arrow keys will allow you to move the v...

Страница 58: ...en the test will end Segments All the segments on the LCD are lit up so you can see if they all work Press ENTER to end the test Keys You should press each key to confirm it works with a counter showi...

Страница 59: ...ed Check that the correct Device Address Modbus ID for the FlowPulse has been entered into P142 of the Flow Monitor Current velocity reads zero but you know there is flow movement Ensure FlowPulse sen...

Страница 60: ...nsducer in accordance with regional environmental regulations for electrical electronic products Controllers Remove power disconnect the Controller and remove battery if fitted Dispose of Controller i...

Страница 61: ...Page 55...