- Press the "OK" button - the calibration procedure is started (see section 6.2)
-
To return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons
5.5.3. Setting the EPS output delay -
"EPS”
The power supply has a programmable delay function of the 230V power failure indication. The time after
which the alarm is sounded can be selected from four available ranges:
- 10s (factory setting)
- 1min
- 10min
- 30min
The 230V power failure is indicated by changing the status of the "EPS" and "ALARM" technical outputs.
-
Simultaneously press the „<,>” rightmost and leftmost buttons
and hold for at least 5 seconds
-
The „tSt” parameter will be displayed
-
Use the „<” or „>” buttons in order to display the "EPS" parameter
-
Press „OK”
- The information about the current setting will be displayed
-
Use the „<” or „>” buttons to set the time lag
0.10 - 10s (factory setting)
1.0 - 1min
10.0 - 10min
30.0 - 30min
-
Press the „OK” button to confirm
-
To return to the main menu, simultaneously press the „<,>” rightmost
and leftmost buttons