![Pulsar Measurement IMP Lite Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/pulsar-measurement/imp-lite/imp-lite_instruction-manual_1625416030.webp)
IMP LITE INSTRUCTION MANUAL
30
Display (DiSP) Menu
P800 Display Units
This parameter determines whether the reading displayed is in
Measurement Units
(
P104
), or as a
percentage
of
span.
OPTION
DESCRIPTION
1 = Measured (Default)
Display in
Measurement Units
(P104)
2 = Percentage
Display is in
Percentage
of span
P801 Decimal Places
This parameter determines the number of decimal places on the reading
during run mode.
Minimum = 0 (No decimal places), Maximum 3 = (3 decimal Places)
Default = 2
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display, relays and the mA
output are held at their last
known
values until a valid reading is obtained.
If required, then you can change this so that the unit goes to
high
(100% of
span), or
low
(empty) as follows:
OPTION
DESCRIPTION
1 = Known (Default)
Remain at the last
known
value
2 = High
Will fail to the
high
value (100% of span)
3 = Low
Will fail to the
low
value (empty)
P809 Fail-safe Time
In the event of a fail-safe condition occurring the fail-safe timer determines
the time before fail-safe mode is activated.
Default = 2.00 mins
If the timer activates, the unit goes into
fail-safe
, as determined by
P808
,
(
Display
and
P840
(
mA Output
). When this happens, you will see the
message “
LOE
!” on the display.
When a valid measurement is obtained then the display, relays and mA
output will be restored and the timer is reset.
Содержание IMP Lite
Страница 1: ...IMP Lite Instruction Manual...
Страница 2: ...2...
Страница 9: ...PULSAR MEASUREMENT 9 EU Declaration of Conformity...