PIM90.245

Feb. 2022 / Rev. 2.0 DS-PIM90.245-EN

www.pulspower.com

14 / 18

All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

16. Safety and Protection Features

Isolation resistance

>500MOhm

At delivered condition between input and output,
measured with 500Vdc

>500MOhm

At delivered condition between input and PE,
measured with 500Vdc

>500MOhm

At delivered condition between output and PE,
measured with 500Vdc

Output over-voltage protection

typ. 30.5Vdc
max. 32Vdc

In case of an internal defect, a redundant circuit limits the maximum output 
voltage to 32V. The output shuts down. To attempt a restart, turn the input 
power off for at least 90s.

Class of protection

I

According to IEC 61140

Degree of protection

IP20

According to EN/IEC 60529

Over-temperature protection

Not Included

Input transient protection

MOV (Metal Oxide Varistor) For protection values see chapter 14 (EMC).

Internal input fuse

Included

Not user replaceable slow-blow high-braking
capacity fuse

At 100Vac, 50Hz, TN-, TT-mains / IT-mains
At 120Vac, 60Hz, TN-, TT-mains / IT-mains
At 230Vac, 50Hz, TN-, TT-mains / IT-mains
At 110Vac, 50Hz, TN-, TT-mains / IT-mains
At 132Vac, 60Hz, TN-, TT-mains / IT-mains

Touch current (leakage current)

typ. 

 

 

 

30μA / 60μA 

typ. 

  

 

40μA / 90μA 

typ. 

 

 

 

70μA / 140μA 

max. 

 

40μA / 70μA 

max. 

 

50μA / 110μA 

max. 

 

90μA / 180μA

At 264Vac, 50Hz, TN-, TT-mains / IT-mains

17. Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground.

It is recommended that either the (+) pole or the (–) pole shall be connected to the protective earth system. This helps to
avoid situations in which a load starts unexpectedly or can not be switched off when unnoticed earth faults occur.

Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate
test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together
as well as all output poles before conducting the test. When testing, set the cut-off current settings to the value in the
table below.

Fig. 17-1: Dielectric strength

A

B

C

Type test

60s

2500Vac

3000Vac

1000Vac

Factory test

5s

2500Vac

2500Vac

500Vac

Field test

5s

2000Vac

2000Vac

500Vac

Field test cut-off
current settings

>2mA

>2mA

>6mA

Содержание PIANO PIM90.245

Страница 1: ...rmits surrounding temperatures up to 70 C The PIANO family is a compact industrial grade DIN rail power supply series that focuses on the essential features needed in today s industrial applications The excellent cost performance ratio does not compromise quality or reliability Output voltage DC 24V Nominal Adjustment range 24 28V Factory setting 24 1V Output current 3 8 3 2A Below 60 C ambient 2 ...

Страница 2: ...antly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this document may be reproduced or utilized in any form without our prior permission in writing Packaging and packaging aids can and should always be recycled The product itself may not be disposed of as do...

Страница 3: ...on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operating temperature of 60 C for ambient temperatures up to 45 C 75 C for ambient temperatures up to 60 C and 90 C for ambient temperatures up to 70 C Ensure that all strands of a stranded wire enter the terminal connection Unused...

Страница 4: ...ig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 69A 1 45A 0 95A At 24V 3 8A see Fig 3 1 Power factor typ 0 6 0 58 0 45 At 24V 3 8A see Fig 3 4 Start up delay typ 50ms 50ms 50ms See Fig 3 2 typ 21ms 21ms 20ms At 24V 3 8A constant current load 0mF load capacitance see Fig 3 2 Rise...

Страница 5: ...impact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 14A 18A 40A At 40 C ambient cold start Inrush current Ipeak typ 12A 16A 35A At 25 C ambient cold start max 17A 22A 48A At 40 C ambient cold start max 15A 20A 43A At 25 C ambient cold start Inrush energy I2 t max 0 3A2 s 0 4A2 s...

Страница 6: ... unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 3 8A static value see Fig 6 1 Ripple and noise voltage max 100mVpp Bandwidth 20Hz to 20MHz 50Ohm Output current nom 3 8A At 24V and an ambient temperature below 60 C nom 2 8A At 24V and 70 C ambient temperature nom 3 2A At 28V and an ambient temperature below 60 C nom 2 4A At 28V and 70 C ambient temperatu...

Страница 7: ...voltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on during this time AC 100V AC 120V AC 230V Hold up time typ 14ms 25ms 119ms At 24V 3 8A typ 40ms 60ms 242ms At 24V 1 9A min 11 5ms 20ms 95ms At 24V 3 8A min 32ms 48ms 194ms At 24V 1 9A Fig 7 1 Hold up ...

Страница 8: ... 3W 0 3W 0 4W At no load typ 5W 4 3W 3 8W At 24V 1 9A half load typ 9 5W 7 9W 6W At 24V 3 8A full load The average efficiency is an assumption for a typical application where the device is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with 100 of the nominal load for the rest of the time...

Страница 9: ...V 1 9A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product The MTBF figure is a statistical representation of the likelihood of a device to fail A MTBF figure of e ...

Страница 10: ...Fig 11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Screw terminals Solid wire max 6mm2 Stranded wire max 4mm2 American Wire Gauge AWG 20 10 Max wire diameter including ferrules 2 8mm Wire stripping length 7mm 0 28inch Recommended tightening torque 1Nm 9lb in Screwdriver 3mm slotted or Phill...

Страница 11: ...13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input PE Protective Earth B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally connected Positive output Negative return output C DC OK LED green The LED is on when the output voltage is above 18V Fig 13 1 Front side D Output voltage adustment potentiometer ...

Страница 12: ...n input EN 61000 4 5 L N 2kV Criterion A N L PE 4kV Criterion A Surge voltage on output EN 61000 4 5 1kV Criterion A PE 1kV Criterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Criterion A 0 of 120Vac 0Vac 20ms Criterion A 40 of 120Vac 48Vac 200ms Criter...

Страница 13: ...urrent limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 47kPa See Fig 15 2 for details Altitude Up to 5000m 16 400ft See Fig 15 2 for details Over voltage category III According to IEC 60664 1 for altitudes 2000m II According to IEC 60664 1 for altitudes 2000m Degree of pollution 2 According to 62477 1 non co...

Страница 14: ...00Vac 50Hz TN TT mains IT mains At 120Vac 60Hz TN TT mains IT mains At 230Vac 50Hz TN TT mains IT mains At 110Vac 50Hz TN TT mains IT mains At 132Vac 60Hz TN TT mains IT mains Touch current leakage current typ 30μA 60μA typ 40μA 90μA typ 70μA 140μA max 40μA 70μA max 50μA 110μA max 90μA 180μA At 264Vac 50Hz TN TT mains IT mains 17 Dielectric Strength The output voltage is floating and has no ohmic ...

Страница 15: ...ges up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Duration 3 weeks which simulates a service life of at least 10 years VDMA 24364 Paint Wetting I...

Страница 16: ... rail height must be added to the unit depth to calculate the total required installation depth Weight 270g 0 6lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Housing material High grade polycarbonate ABS blend material Installation clearances See chapter 2 Penetration protection Small parts like screws nuts etc with a diameter larger than 4 2mm Fig 20...

Страница 17: ...LLEL USE TO INCREASE OUTPUT POWER Do not use this devices in parallel to increase the output power 21 4 PARALLEL USE FOR 1 1 REDUNDANCY Devices can be paralleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The simplest way is to put two devices in parallel This is called a 1 1 redundanc...

Страница 18: ...ly The power supply is placed in the middle of the box no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1cm The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure Case A Case B Enclosure size 110x180x165mm Rittal Typ IP66...

Отзывы: