Puls PIANO PIM60.241 Скачать руководство пользователя страница 9

PIM60.241

Feb. 2022 / Rev. 2.0 DS-PIM60.241-EN

www.pulspower.com

9 / 17

All parameters are specified at 24V, 2.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

9.

Lifetime Expectancy

The  Lifetime  expectancy  shown  in  the  table  indicates  the  minimum  operating  hours  (service  life)  and  is  determined  by
the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is
calculated according to the capacitor’s manufacturer specification.

Please note: The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h).
Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

AC 100V

AC 120V

AC 230V

Lifetime expectancy

115 000h

131 000h

148 000h

At 24V, 2.5A and 40°C

260 000h

263 000h

263 000h

At 24V, 1.25A and 40°C

324 000h

370 000h

419 000h

At 24V, 2.5A and 25°C

734 000h

744 000h

744 000h

At 24V, 1.25A and 25°C

10. MTBF

MTBF  stands  for  Mean  Time  Between  Failure,  which  is  calculated  according  to  statistical  device  failures,  and  indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent
the life of a product.

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means
that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined
if the failed unit has been running for 50 000h or only for 100h.

For these types of units the MTTF (Mean Time TFailure) value is the same value as the MTBF value.

AC 100V

AC 120V

AC 230V

MTBF SN 29500, IEC 61709

1 797 000h

1 858 000h

1 982 000h

At 24V, 2.5A and 40°C

3 093 000h

3 186 000h

3 378 000h

At 24V, 2.5A and 25°C

MTBF MIL HDBK 217F

868 000h

886 000h

803 000h

At 24V, 2.5A and 40°C; Ground Benign GB40

1 257 000h

1 278 000h

1 175 000h

At 24V, 2.5A and 25°C; Ground Benign GB25

247 000h

252 000h

247 000h

At 24V, 2.5A and 40°C; Ground Fixed GF40

325 000h

331 000h

328 000h

At 24V, 2.5A and 25°C; Ground Fixed GF25

Содержание PIANO PIM60.241

Страница 1: ...rounding temperatures up to 70 C The unit is designed as Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO famil...

Страница 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Страница 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Страница 4: ...Fig 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 15A 1A 0 6A At 24V 2 5A see Fi...

Страница 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 12A 15A 36A At 40 C ambient...

Страница 6: ...value which can be achieved Factory settings typ 24 1V 0 2 at full load cold unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 2 5A static value see Fig 6 1...

Страница 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Страница 8: ...W 0 3W 0 4W At no load typ 3 8W 3 5W 3 4W At 24V 1 25A half load typ 7 1W 6 2W 5 4W At 24V 2 5A full load The average efficiency is an assumption for a typical application where the device is loaded w...

Страница 9: ...V 1 25A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representati...

Страница 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Страница 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Страница 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Страница 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Страница 14: ...ins IT mains typ 100 A 200 A At 230Vac 50Hz TN TT mains IT mains max 60 A 100 A At 110Vac 50Hz TN TT mains IT mains max 80 A 150 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current max...

Страница 15: ...ts for supply voltages up to 1100V Particular requirements and tests for switch mode power supply units and transformers for switch mode power supply units ISA 71 04 1985 Manufacturer s Declaration On...

Страница 16: ...eight Width 36mm 1 42 Height 90mm 3 54 Depth 91mm 3 58 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 225g 0 5lb DIN rail Use 35mm DIN ra...

Страница 17: ...NDANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phas...

Отзывы: