ML120.244
MiniLine-2
24V,
5A,
S
INGLE
P
HASE
I
NPUT
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.12.
M
OUNTING
O
RIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1
Recommended output current.
Curve A2
Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 22-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Output Power
10
20
30
40
60°C
50
A1
Ambient Temperature
0
1A
3A
4A
5A
2A
Fig. 22-6
Mounting
Orientation B
(Upside down)
Powe
r
Supply
OUTPUT
INPUT
Output Power
10
20
30
40
60°C
50
A1
A2
Ambient Temperature
0
1A
3A
4A
5A
2A
Fig. 22-7
Mounting
Orientation C
(Table-top
mounting)
Output Power
10
20
30
40
60°C
50
A1
A2
Ambient Temperature
0
1A
3A
4A
5A
2A
Fig. 22-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
IN
PU
T
Output Power
10
20
30
40
60°C
50
A1
A2
Ambient Temperature
0
1A
3A
4A
5A
2A
Fig. 22-9
Mounting
Orientation E
(Horizontal ccw)
Power Supply
OUTPUT
IN
PU
T
Output Power
10
20
30
40
60°C
50
A1
A2
Ambient Temperature
0
1A
3A
4A
5A
2A
21/21