Puls MiniLine-2 Series Скачать руководство пользователя страница 19

 

 

ML120.244

 

 

MiniLine-2 

 

24V,

 

5A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

22.6.

 

P

ARALLEL 

U

SE FOR 

R

EDUNDANCY

 

MLY10.241

IN 1

+

-

+

-

L
N

I

I

ML120.244

L    N

Output

Input

+  +

-  -

ML120.244

L    N

Output

Input

+  +

-  -

Output

Load

+

-  -

+

-

IN 2

Voltage
Monitor

Power supplies can be paralleled for redundancy to gain higher 
system availability. Redundant systems require a certain amount of 
extra power to support the load in case one power supply unit fails. 
The simplest way is to put two power supplies in parallel. This is called 
a 1+1 redundancy. In case one power supply unit fails, the other one is 
automatically able to support the load current without any 
interruption. Redundant systems for a higher power demand are 
usually built in a N+1 method. E.g. five power supplies, each rated for 
5A are paralleled to build a 20A redundant system. 

 

Please note:

 This simple way to build a redundant system does not 

cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defect unit 
becomes a load for the other power supplies and the output voltage can not be maintained any more. This can only be 
avoided by utilizing decoupling diodes which are included in the redundancy module MLY10.241 or YRM2.DIODE. 

Recommendations for building redundant power systems: 

a)

 

Use separate input fuses for each

 

power supply. 

b)

 

Use separate mains systems for each power supply whenever it is possible. 

c)

 

Monitor the individual power supply units. A monitoring circuit is included in the DIMENSION redundancy 
module YRM2.DIODE, which can also be used as a redundancy module for the ML120.241 units. 

d)

 

1+1 Redundancy is allowed up to an ambient temperature of 60°C. 
N+1 Redundancy is allowed up to an ambient temperature of 45°C. 

e)

 

It is desirable to set the output voltages of all units to the same value (± 100mV) or leave it at the factory setting. 

 

22.7.

 

D

AISY 

C

HAINING OF 

O

UTPUTS

 

Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current 
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block. 

 

Fig. 22-3   Daisy chaining of outputs 

 

Fig. 22-4   Using distribution terminals 

 

Load

+

-

Power

Supply

+  +

-

 

-

Output

max 25A!

continuous

Power

Supply

+  +

-

 

-

Output

 

 

Load

+

-

Distribution

Terminals

Power

Supply

+  +

-  -

Input

Output

Power

Supply

+  +

-  -

Input

Output

 

 

22.8.

 

I

NDUCTIVE AND 

C

APACITIVE 

L

OADS

 

The unit is designed to supply any type of load, including unlimited capacitive and inductive loads. 

Apr. 2013 / Rev. 1.1  DS-ML120.244-EN  
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

19/21

Содержание MiniLine-2 Series

Страница 1: ...vironment Besides the cost optimized ML120 244 two additional units are available in the ML120 series The ML120 CLASS2 fulfills the NEC Class 2 requirements and the ML120 241 is the standard product w...

Страница 2: ...housing is patent by PULS US patent No US D442 923S No part of this document may be reproduced or utilized in any form without permission in writing from the publisher TERMINOLOGY AND ABREVIATIONS PE...

Страница 3: ...le another power supply WARNING Risk of electrical shock fire personal injury or death Do not use the power supply without proper grounding Protective Earth Use the terminal on the input block for ear...

Страница 4: ...down voltage typ 134Vac steady state value see Fig 3 1 The power factor is the ratio of the true or real power to the apparent power in an AC circuit The crest factor is the mathematical ratio of the...

Страница 5: ...t Inrush energy typ 1A2 s 40 C ambient cold start Fig 4 1 Input inrush current typical behavior 230Vac input 24V 5A output 25 C ambient Fig 4 2 Input inrush current zoom into first peak 230Vac input 2...

Страница 6: ...ll output voltage cannot be maintained and the output voltage will drip to lower values Detailed curves can be found in chapter22 1 Output power nom 120W Short circuit current min 7 8A load impedance...

Страница 7: ...ing this time Fig 7 1 Hold up time vs input voltage Fig 7 2 Shut down behavior definitions 0 15 30 75 90ms 200 210 230 240 260Vac Hold up Time 45 60 a b c d 220 Input Voltage 250 a 24V 2 5A typ b 24V...

Страница 8: ...0 of the nominal load for the rest of the time Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 0 5 84 85 86 87 88 89 90 83 91 5A 2 2 5 4 1 3 Outp...

Страница 9: ...t Terminals Screw terminals Dual terminals for the negative and positive pole Both poles are equal Positive output Negative return output B Input Terminals Screw terminals L Phase Line input N Neutral...

Страница 10: ...and 40 C 96 000h at 24V 2 5A and 40 C 106 000h at 24V 5A and 25 C MTBF SN 29500 IEC 61709 T B D at 24V 5A and 40 C T B D at 24V 5A and 25 C MTBF MIL HDBK 217F T B D at 24V 5A 40 C Ground Benign GB40 T...

Страница 11: ...est During the test minor temporary impairments may occur which will be corrected by the power supply itself C Temporary loss of function is possible Power supply may shut down and restarts by itself...

Страница 12: ...er voltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release a...

Страница 13: ...Hz TN TT mains IT mains Double or reinforced insulation 17 DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground Type and factory tests are conducted by the manu...

Страница 14: ...vel 3 in U S A UL 60950 1 and Canada C22 2 No 60950 1 E File E137006 Marine pending Marine and offshore applications environmental category C EMC2 GL Germanischer Lloyd classified GOST P pending Certi...

Страница 15: ...he DIN rail height must be added to the unit depth 103mm to calculate the total required installation depth Installation Clearances See chapter 2 Fig 20 1 Front view Fig 20 2 Side view Apr 2013 Rev 1...

Страница 16: ...hold up time DC Buffer Unit s Power Supply Load AC 21 2 REDUNDANCY MODULES The MLY10 241 is a dual redundancy module which has two diodes with a common cathode included It can be used for various pur...

Страница 17: ...ow typical voltage dips Fig 22 1 Peak loading with 2x the nominal current for 50ms typ Fig 22 2 Peak loading with 5x the nominal current for 5ms typ 10ms DIV Output Voltage Output Current 24 5V 0A 10A...

Страница 18: ...load current between the power supplies Usually the power supply with the higher adjusted output voltage draws current until it goes into current limitation This means no harm to the power supply as l...

Страница 19: ...ng redundant power systems a Use separate input fuses for each power supply b Use separate mains systems for each power supply whenever it is possible c Monitor the individual power supply units A mon...

Страница 20: ...ed as long as the supplying voltage is below 240V 10 Use a fuse or a circuit breaker to protect the N input The N input is not internally protected and is in this case connected to a hot wire Appropri...

Страница 21: ...ended output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 5 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outp...

Отзывы: