ML120.244
MiniLine-2
24V,
5A,
S
INGLE
P
HASE
I
NPUT
15.
P
ROTECTION
F
EATURES
Output protection
Electronically protected against overload, no-load and short-circuits
*)
Output over-voltage protection typ.
31Vdc
max. 33Vdc
In case of an internal power supply fault, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Output over-current protection electronically
limited
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 2.5mm in diameter
e.g. screws, small parts
Over-temperature protection
not included
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
T3.15A H.B.C.
not user replaceable
*) In case of a protection event, audible noise may occur.
16.
S
AFETY
F
EATURES
Input / output separation
SELV
*)
IEC/EN
60950-1
PELV
*)
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
Class of protection
I
PE (Protective Earth) connection required
Isolation resistance
> 5MOhm
Input to output, 500Vdc
Touch current (leakage current)
typ. 0.56mA / 1.17mA
230Vac, 50Hz, TN-,TT-mains / IT-mains
< 0.75mA / 1.45mA
264Vac, 50Hz, TN-,TT-mains / IT-mains
*) Double or reinforced insulation
17.
D
IELECTRIC
S
TRENGTH
The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by
the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the
voltage with a slow ramp (2s up and 2s down). Connect all phase-terminals together as well as all output poles before
conducting the test. When testing, set the cut-off current settings to the value in the table below.
Fig. 17-1
Dielectric strength
A B C
Type test
60s
2500Vac
3500Vac
1000Vac
Factory test
5s
2500Vac
2500Vac
500Vac
Field test
5s
2000Vac
2000Vac
500Vac
Cut-off current setting
> 10mA
> 10mA
> 20mA
A
C
N
L
Input
Earth, PE
Output
-
+
B
To fulfill the PELV requirements according to EN 60204-1 § 6.4.1,
we recommend that either the + pole, the – pole or any other part
of the output circuit shall be connected to the protective earth
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
Apr. 2013 / Rev. 1.1 DS-ML120.244-EN
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/21