ML120.244

 

 

MiniLine-2 

 

24V,

 

5A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

13.

 

EMC 

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available on request. 

 

EMC Immunity 

Generic standards: EN 61000-6-1 and EN 61000-6-2 

Electrostatic discharge  

EN 61000-4-2 

Contact discharge 
Air discharge 

8kV 
8kV 

Criterion A 
Criterion A 

Electromagnetic RF field 

EN 61000-4-3 

80MHz-2.7GHz 

10V/m 

Criterion A 

Fast transients (Burst) EN 

61000-4-4 

Input 

lines 

Output lines 
DC-OK Signal (coupling clamp) 

4kV 
2kV 
2kV 

Criterion A 
Criterion A 
Criterion A 

Surge voltage on input 

EN 61000-4-5 

Æ

 N 

Æ

 PE, L 

Æ

 PE 

2kV 
4kV 

Criterion A 
Criterion A 

Surge voltage on output 

EN 61000-4-5 

Æ

 - 

Æ

 PE, - 

Æ

 PE 

1kV 
2kV 

Criterion A 
Criterion A 

Conducted disturbance 

EN 61000-4-6 0.15-80MHz 

10V 

Criterion 

Mains voltage dips 

EN 61000-4-11 

0% of 200Vac

 

40% of 200Vac 
70% of 200Vac 

0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 

Criterion A 
Criterion A 
Criterion A 

Voltage interruptions 

EN 61000-4-11 

 

0Vac, 5000ms 

Criterion C 

Input voltage swells 

PULS internal standard 

300Vac, 500ms 

Criterion A 

Powerful transients 

VDE 0160 

over entire load range 

750V, 1.3ms 

Criterion A 

Criterions:

 

A:

    Power supply shows normal operation behavior within the defined limits. 

B:

 

The power supply operates continuously during and after the test. During the test minor temporary impairments may occur, which will be 
corrected by the power supply itself. 

C:

    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 

will occur. 

 

EMC Emission 

Generic standards: EN 61000-6-3 and EN 61000-6-4 

Conducted emission 
input lines 

EN 55011, EN 55022, FCC Part 15, 
CISPR 11, CISPR 22 

Class B 

Conducted emission  
output lines 

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 

Limits for DC power port acc. EN 
61000-6-3 not fulfilled

**)

 

Radiated emission 

EN 55011, EN 55022, CISPR 11, CISPR 22 

Class B 

Harmonic input current 

EN 61000-3-2 

Class A fulfilled 

Voltage fluctuations, flicker

*)

 EN 

61000-3-3 

Fulfilled 

This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 

*) 

tested with constant current loads, non pulsing 

**)  Restrictions apply for applications in residential, commercial and light-industrial environments, where local DC power networks according 

to EN 61000-6-3 are involved. No restrictions for all kinds of industrial applications. 

 

Switching frequency 

 

 

Converter frequency 

variable, typ. 100kHz, min. 60kHz, max. 260kHz 

Input voltage and output 
load dependent 

Apr. 2013 / Rev. 1.1  DS-ML120.244-EN  
All parameters are specified at 24V, 5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

11/21

Содержание MiniLine-2 Series

Страница 1: ...vironment Besides the cost optimized ML120 244 two additional units are available in the ML120 series The ML120 CLASS2 fulfills the NEC Class 2 requirements and the ML120 241 is the standard product w...

Страница 2: ...housing is patent by PULS US patent No US D442 923S No part of this document may be reproduced or utilized in any form without permission in writing from the publisher TERMINOLOGY AND ABREVIATIONS PE...

Страница 3: ...le another power supply WARNING Risk of electrical shock fire personal injury or death Do not use the power supply without proper grounding Protective Earth Use the terminal on the input block for ear...

Страница 4: ...down voltage typ 134Vac steady state value see Fig 3 1 The power factor is the ratio of the true or real power to the apparent power in an AC circuit The crest factor is the mathematical ratio of the...

Страница 5: ...t Inrush energy typ 1A2 s 40 C ambient cold start Fig 4 1 Input inrush current typical behavior 230Vac input 24V 5A output 25 C ambient Fig 4 2 Input inrush current zoom into first peak 230Vac input 2...

Страница 6: ...ll output voltage cannot be maintained and the output voltage will drip to lower values Detailed curves can be found in chapter22 1 Output power nom 120W Short circuit current min 7 8A load impedance...

Страница 7: ...ing this time Fig 7 1 Hold up time vs input voltage Fig 7 2 Shut down behavior definitions 0 15 30 75 90ms 200 210 230 240 260Vac Hold up Time 45 60 a b c d 220 Input Voltage 250 a 24V 2 5A typ b 24V...

Страница 8: ...0 of the nominal load for the rest of the time Fig 8 1 Efficiency vs output current at 24V typ Fig 8 2 Losses vs output current at 24V typ Efficiency 0 5 84 85 86 87 88 89 90 83 91 5A 2 2 5 4 1 3 Outp...

Страница 9: ...t Terminals Screw terminals Dual terminals for the negative and positive pole Both poles are equal Positive output Negative return output B Input Terminals Screw terminals L Phase Line input N Neutral...

Страница 10: ...and 40 C 96 000h at 24V 2 5A and 40 C 106 000h at 24V 5A and 25 C MTBF SN 29500 IEC 61709 T B D at 24V 5A and 40 C T B D at 24V 5A and 25 C MTBF MIL HDBK 217F T B D at 24V 5A 40 C Ground Benign GB40 T...

Страница 11: ...est During the test minor temporary impairments may occur which will be corrected by the power supply itself C Temporary loss of function is possible Power supply may shut down and restarts by itself...

Страница 12: ...er voltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release a...

Страница 13: ...Hz TN TT mains IT mains Double or reinforced insulation 17 DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground Type and factory tests are conducted by the manu...

Страница 14: ...vel 3 in U S A UL 60950 1 and Canada C22 2 No 60950 1 E File E137006 Marine pending Marine and offshore applications environmental category C EMC2 GL Germanischer Lloyd classified GOST P pending Certi...

Страница 15: ...he DIN rail height must be added to the unit depth 103mm to calculate the total required installation depth Installation Clearances See chapter 2 Fig 20 1 Front view Fig 20 2 Side view Apr 2013 Rev 1...

Страница 16: ...hold up time DC Buffer Unit s Power Supply Load AC 21 2 REDUNDANCY MODULES The MLY10 241 is a dual redundancy module which has two diodes with a common cathode included It can be used for various pur...

Страница 17: ...ow typical voltage dips Fig 22 1 Peak loading with 2x the nominal current for 50ms typ Fig 22 2 Peak loading with 5x the nominal current for 5ms typ 10ms DIV Output Voltage Output Current 24 5V 0A 10A...

Страница 18: ...load current between the power supplies Usually the power supply with the higher adjusted output voltage draws current until it goes into current limitation This means no harm to the power supply as l...

Страница 19: ...ng redundant power systems a Use separate input fuses for each power supply b Use separate mains systems for each power supply whenever it is possible c Monitor the individual power supply units A mon...

Страница 20: ...ed as long as the supplying voltage is below 240V 10 Use a fuse or a circuit breaker to protect the N input The N input is not internally protected and is in this case connected to a hot wire Appropri...

Страница 21: ...ended output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 5 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Outp...

Отзывы: