FPS300.245-049-102
All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
5 / 28
AC-Input
The device is suitable to be supplied from TN, TT or IT mains networks. For more details, please review chapter 2.
AC input voltage rated range nom.
AC 100-240 V
AC input operating range
85-264 Vac
Continuous operation
264-300 Vac
For maximal 500ms
Input frequency
Nom. 50–60 Hz
±6 %
Turn-on voltage
Typ.
80 Vac
Steady-state value, see Fig. 3-1
Shut-down voltage
Typ.
70 Vac
Steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 2 .
AC 100 V AC 120 V AC 230 V
Input current
typ.
3.98 A
3.2 A
1.68 A
At 360 W, symmetrical phase voltages, see Fig. 3-3 Power
Power factor
*)
typ.
0.99
0.99
0.97
At 360 W, see Fig. 3-4
Start-up delay
typ.
2 s
2 s
2 s
At 300 W symmetrical phase voltages, see Fig. 3-2
Rise time
typ.
22 ms
22 ms
22 ms
At 300 W constant current load, 0mF load, see Fig. 3-2
typ.
48 ms
46 ms
35 ms
At 300 W constant current load, 12.5mF, see Fig. 3-2
Turn-on
overshoot
Max.
200 mV
200 mV
200 mV
See Fig. 3-2
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
Fig. 3-1: Input voltage range
Fig. 3-2: Turn-on behavior, definitions
Fig. 3-3:
Input current vs. output power at 24 V output
voltage
Fig. 3-4:
Power factor vs. output power at 24 V output
voltage
85V
AC input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Tu
rn
-on
Shut
-dow
n
L1
Start-up
delay
Rise
Time
O
ve
rs
hoot
Output
Voltage
Input
Voltage
-5%
A
B
C
A
100Vac
C
230Vac
B
120Vac
Input Current (A)
Output Power (W)
0
2
1
3
5
4
360
260
60
160
-40
A
B
C
A
100Vac
C
230Vac
B
120Vac
Power Factor (1)
Output Power (W)
0,70
0,75
0,80
0,85
0,90
0,95
1,00
360
260
60
160
-40