All parameters are specified at 24 V, 12.5 A, 230 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.

 

Apr. 2022 / Rev. 0.2 FPS300-EN 

www.pulspower.com 

10 / 43 

 

 

IO-Link Interface 

The IO-Link interface used in this power supply is compliant to IO-Link protocol V1.1 and can be connected to any IO-Link 
masters compliant to V1.1 of the IO-Link protocol. This allows a transparent data flow to the sensors and actuators and 
therefore more transparent and easier way to monitor the current status of the power supply. 
 

In case of no or defective connectivity of the IO-Link, the power supply can also be operated on smoothly. Due to a built-
in EEPROM, previously inputted data will be drawn from its storage. 
 
To operate the IO-Link interface it is required to install/upload the IODD-File (IO-Link Device Description) into the connected 
IO-Link master. The most recent IODD file can be found on the PULS website (www.pulspower.com) in the download section 
of the individual product page. The device can also be accessed via IO-Link, if the power supply is not connected to AC-
mains and in a switched off mode. 
 

IO-Link Version 

V1.1 

To get full performance, it is recommended to use IO-Link

 

IO-Link master Version 

V1.1 

 

Baud-Rate

 

COM3 (230.4 kBaud)

 

 

Cycle Time 

2ms 

Cycle time refers to the reloading speed of certain process data 

SIO-Mode

 

yes 

Class B 

Process Data Length

 

23 bytes

 

 

 
The  power supply provides three categories of data via IO-Link. They are divided between read only or read-  and 

customizable data. 
 

Control Settings 

This set of data is customizable. The data in control settings can be adjusted to the user’s preference to ensure an even 
better operation of the power supply. Typical control settings are e.g. setting tripping points, setting per-alarm levels, etc.  
 

Parameter write  

Value range 

Description 

Output Voltage Setpoint 

24.0-28.0 V 

Output Voltage Setpoint 
Pre-Setting- 24.5 V 

Standby 

0 - unit is operating 
1 - unit in standby 

PSU can be switched into standby, where all outputs 
turn off. 

Pre-Setting- 0=unit is operating 

Configuration Setting 

0 - human-machine interface 
only 
1 - IO-Link only 
2 - both 
3 - none (button lock) 

Controls the configurability of the PSU, which can be 
restricted to local HMI or IO-Link only. 
Configuration can also be blocked completely. 
Pre-Setting- 2=both 

E-Fuse Channel on/off 

0 – off 
1 - on 

Used to control the state of output channel switches 
(ON/OFF) or to reconnect a tripped channels. 

Bit coded parameter. 
Pre-Setting- 1=ON for all channels 

E-Fuse trip value 
channel 1 to channel 4 

1-10/12 A 

Defines the output current threshold for each E-Fuse 
channel, where the electronic fuse is triggered. 
Pre-Setting- 10/12 A (depends on type of output 
connector) 

E-Fuse Pre-alarm level 
channel 1 to channel 4 

10-100 % 

Defines the threshold for the event 
"Output current pre-alarm for each channel". 

Pre-Setting- 80 % 

PSU total output current 
Pre-alarm level 

1-100 A 

Defines the threshold for the event 
"PSU output current pre-alarm". 
To suppress event generation, set this value to max 
(100 A). 
Pre-Setting- 20A 

 

 

 

Содержание FIEPOS FPS300.246-036-104

Страница 1: ...and store regenerative energy from breaking motors Various connector options support the different needs of individual applications Please contact PULS for possible options High immunity to transient...

Страница 2: ...s the state of our knowledge and experience is constantly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document...

Страница 3: ...Phase IP54 67 Power Supply Highline Input Voltage 300 300 W Power Class 500 500 W Power Class 241 481 Standard Power Supply with Output Voltage 24 28 V 48 52 V Setting and LED Bar 242 482 Basic Power...

Страница 4: ...rviceable parts The tripping of an internal fuse is caused by an internal defect Install the device onto a flat surface with the terminals on the bottom of the device Other mounting orientations requi...

Страница 5: ...3 3 Power Power factor typ 0 99 0 99 0 97 At 360 W see Fig 3 4 Start up delay typ 2 s 2 s 2 s At 300 W symmetrical phase voltages see Fig 3 2 Rise time typ 22 ms 22 ms 22 ms At 300 W constant current...

Страница 6: ...Fig 4 1 Wiring for DC Input Instructions for DC use a Use a battery or a similar DC source A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunctio...

Страница 7: ...highest number will tripped first followed by the next output to ensure that the lower channel number will supply continuous power and see no voltage dips Outputs start sequentially from 1 to 4 with...

Страница 8: ...0 Vac 25 C ambient and after a 5 minutes run in time unless otherwise noted Apr 2022 Rev 0 2 FPS300 EN www pulspower com 8 43 Fig 6 1 Sequential start of the outputs Fig 6 2 Tripping of the channel wi...

Страница 9: ...the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The status LED is also on during this time AC 100V AC 120V AC 230V Hold up T...

Страница 10: ...er supply provides three categories of data via IO Link They are divided between read only or read and customizable data Control Settings This set of data is customizable The data in control settings...

Страница 11: ...ector E Fuse Pre alarm level channel 1 to channel 4 10 100 Defines the threshold for the event Output current pre alarm for each channel Pre Setting 80 PSU total output current Pre alarm level 1 100 A...

Страница 12: ...rcuit trip 3 Temperature trip 4 Power budget trip 5 Installation failure trip 6 Sensor fault trip 7 Fatal fault trip Actual trip state of E Fuse channel If the E Fuse has tripped this parameter gives...

Страница 13: ...utes 0 1000000 0 59 Total operating hours operating minutes Transient VDE 0160 Counter overall 0 150000 Transient Counter overall Transient VDE 0160 Counter last 2 minutes 0 65535 Transient Counter la...

Страница 14: ...m for more than 3s Events Over Load Warning Load higher than allowed Events High Voltage Input Warning Input to high Events Low Voltage Input Warning Input to low Events Power Supply down Warning No l...

Страница 15: ...actual output voltage of each output channel internal temperatures tripping status reports etc Process Value range Description Actual Output total Current A Actual Output Voltage V Actual Output Volta...

Страница 16: ...application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with...

Страница 17: ...34 400h At 24V 6 25A and 25 C MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical re...

Страница 18: ...fied at 24 V 12 5 A 230 Vac 25 C ambient and after a 5 minutes run in time unless otherwise noted Apr 2022 Rev 0 2 FPS300 EN www pulspower com 18 43 Functional Diagram Fig 12 1 Functional Diagram FPS3...

Страница 19: ...lycarbonate Depth 59 mm 2 32 Installation clearances See chapter 2 Weight 1200 g 2 7lb Mating connectors See chapter 21 3 Input connector on power supply X1 M12 S 3pin Male Pin PE connection Pin 1 L P...

Страница 20: ...ial Hi grade polycarbonate Depth 59 mm 2 32 Installation clearances See chapter 2 Weight 1200 g 2 7lb Mating connectors See chapter 21 3 7 8 3pin Male Pin PE connection Pin 2 L Pin 3 N IO Link connect...

Страница 21: ...The Output Controls consist of an output LED and an Output ON OFF button ON OFF for each output The Output LED displays different running conditions for output in real time The ON OFF is used to switc...

Страница 22: ...oint Refer to the current scale on the right sidebar e g 20 LED indicates 24 5 V New point is set After 15 s of non action the PSU will automatically switch to Output Power Mode Set Button Lock To act...

Страница 23: ...button PSU with NEC Class II outputs Difference between positive and negative Input Output current of the output are 1 A for 6 6 5 s PSU without NEC Class II outputs Connector negative wire overcurre...

Страница 24: ...V Criterion A L to PE N to PE 4kV Criterion A Surge voltage on DC output EN 61000 4 5 to 1kV Criterion A to PE 2kV Criterion A Surge voltage on IO Link EN 61000 4 5 IO Link to PE 1kV Criterion A Condu...

Страница 25: ...ics EN 61000 3 2 Class A fulfilled between 0A and 12A load Voltage fluctuations flicker EN 61000 3 3 Pass tested with constant current loads non pulsing This device complies with FCC Part 15 rules Ope...

Страница 26: ...ails Over voltage category III According to IEC 60664 1 For TN TT mains systems with earthed neutral and IT star mains systems with insulation monitoring for altitudes up to 2000 m II According to IEC...

Страница 27: ...utput shuts down and automatically attempts to restart Class of protection According to IEC 61140 A PE Protective Earth connection is required Ingress protection IP 65 67 According to EN IEC 60529 Ove...

Страница 28: ...inforced insulation Type and routine tests are conducted by the manufacturer Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp 2...

Страница 29: ...ested for AC 208V L L or L N mains voltages nominal output voltage and nominal output load VDMA 24364 Paint Wetting Impairment Substances Test or LABS Test Tested for Zone 2 and test class C1 accordin...

Страница 30: ...S300 EN www pulspower com 30 43 Accessories 21 1 DIN RAIL Mounting KIT ZM FPDRA 11 In addition to screw mounting FIEPOS can easily be attached to a DIN rail using the ZM FPDRA 11 DIN rail mounting kit...

Страница 31: ...S female 2 5 6mm 14 17mm Harting HANQ2 0 ZCM hanq20 6104401263900 Q2 0 Set screw male 2 5 6mm 6 12mm Harting HANQ4 0 ZCM hanq40 6104401265100 Q4 0 Set crimp 2 5mm2 IP67 Harting HANQ5 0 ZCF hanq50 6104...

Страница 32: ...e DC 24V Nominal Adjustment range 24 28Vdc Factory setting 24 5V Output power Continuous 360W Up to 45 C ambient 300W At 55 C ambient 150W At 70 C ambient Short term up to 5s 600W Below 55 C ambient 3...

Страница 33: ...cified continuous output current If the R M S current is higher the unit may respond with a thermal shut down after a period of time 23 2 External Input Protection The device is designed tested and ap...

Страница 34: ...this datasheet apply only for the standard mounting orientation The following curves give an indication for allowed output power in different mounting orientations for altitudes up to 2000 m 6560 ft A...

Страница 35: ...d PLCs without configuration Process Sub index Bit offset Data type Bit length Data Format Resolution Allowed values Actual Output total Current 1 88 uint16_t 16 Q8 8 2 8 A bit Actual Output Voltage 2...

Страница 36: ...Apr 2022 Rev 0 2 FPS300 EN www pulspower com 36 43 Octet 0 1 2 3 4 5 6 7 8 9 Subindex 1 1 2 2 3 3 4 4 5 5 Bit offset 119 112 111 104 103 96 95 88 87 80 79 72 71 64 63 56 55 48 47 40 Octet 10 Subindex...

Страница 37: ...2 both default value 3 none button lock Dynamic E Fuse Channel on off 106 0 bool array 8 bit Record 1 R W 0 off 1 on Dynamic Bit 3 7 not used Access via subindex 0 only Chanel 1 0 Chanel 2 1 Chanel 3...

Страница 38: ...2 Output current is 5 more than maximum for more than 3s Over Temperature CAP 4 3 bool R bit 3 Temperature Capacitor is higher than 95 C Over Temperature PSU 5 4 bool R bit 4 Temperature of PSU is hig...

Страница 39: ...put voltage 79 0 uint16 15 0 Q8 8 2 8 V bit R 0 12544 0 49V Actual average output voltage Actual output current 81 0 uint16 15 0 Q8 8 2 8 V bit R 0 12800 0 50V Actual average output current E Fuse cur...

Страница 40: ...pr 2022 Rev 0 2 FPS300 EN www pulspower com 40 43 Parameter Para Index Sub index Data type Bit offset Data Format Resolution Default values Read R Write W Allowed values Description Remaining Enduranc...

Страница 41: ...mber of Overcurrents all CHs 88 0 uint16 array 47 0 0 R Number of Overcurrents all Channels E Fuse Number of Overcurrents CH1 1 uint16 47 32 Number of Overcurrents Channel 1 E Fuse Number of Overcurre...

Страница 42: ...tatus 36 0 uint8 7 0 R 0 Device is operating properly 1 Maintenance Required 2 Out of Specification 3 Functional Check 4 Failure 0 Device is operating properly 1 Maintenance Required 2 Out of Specific...

Страница 43: ...t 0x1804 Warning Input to low Events Power Supply down 0x1805 Warning No link from IO Link Transceiver to Power Supply Events Predictive Maintenance Power Supply 0x1806 Warning The estimated remaining...

Отзывы: