background image

 

 

YR40.245

 

 

Y-Series 

12-28V,

 

40A,

 

S

INGLE 

R

EDUNDANCY 

M

ODULE

 

 

 

 

M

OSFET 

R

EDUNDANCY 

M

ODULE

 

ƒ

 

Single Input with Single Output 

ƒ

 

Equipped with Plug-connector for “Hot Swapping” 

ƒ

 

Suitable for all DIMENSION Power Supplies  
Except QT40 Series 

ƒ

 

Only 150mV Voltage Drop at 40A 

ƒ

 

Only 6.2W at 40A 

ƒ

 

160% (65A) Peak Load Capability 

ƒ

 

Reverse Input Polarity Protection 

ƒ

 

Full Power Between -40°C and +60°C 

ƒ

 

Width only 46mm 

ƒ

 

Rugged Metal Housing 

ƒ

 

Easy Wiring: 
Distribution Terminal for Negative Pole Included 

ƒ

 

3 Year Warranty 
 

 

 

 

1/18

G

ENERAL 

D

ESCRIPTION

 

The YR40.245 is a redundancy module, which can be 
used to build redundant systems. The module has one 
input and one output and can carry nominal currents up 
to 40A. The output is equipped with a plug-connector, 
which allows replacing the power supply or the 
redundancy module while the system is running (hot-
swapping)  

The novelty of this redundancy module is the utilization 
of mosfets instead of diodes for the decoupling of the 
two input channels. This reduces the heat generation 
and the voltage drop between input and output. The 
redundancy module does not require an additional 
auxiliary voltage. 

Due to the low power losses, the unit is very slender and 
only requires 46mm width on the DIN-rail. Large 
connection terminals allow for a safe and fast 
installation. The large international approval package 
makes this unit suitable for nearly every application. 

 

S

HORT

-

FORM 

D

ATA

 

 

Input voltage 

DC 12-28V 

±30% 

Input voltage 
range 

8.4-36.4Vdc 

 

Input current 

0-40A  

continuous 

 

40-65A 

for 5 seconds 

Output current 

0-40A 

continuous 

 

40-65A 

for 5 seconds 

 

max. 22A 

in overload

*)

 or 

short circuit mode 

Input to output 
voltage drop 

typ. 80mV 
typ. 150mV 

at 20A 
at 40A 

Power losses 

typ. 120mW 

at no load 

 

typ. 1.8W 

at 24V, 20A 

 

typ. 6.2W 

at 24V, 40A 

Temperature range -40°C to +70°C  operational 
Derating 

1A/°C 

+60 to +70°C 

Dimensions 

*)

 

46x124x127mm WxHxD 

Weight 340g, 

0.75lb 

 

   *)    Currents at voltages below 6V 
   **)  Plus height for plug connector 

 

 

O

RDER 

N

UMBERS

 

Redundancy 

YR40.245

 

12-28V Standard unit 

Module 

Accessory 

ZM2.WALL 

Wall/ panel mount 

  bracket 
 ZM12.SIDE 

Side 

mount 

bracket 

 

M

ARKINGS

 

 

IND. CONT. EQ.

 

UL 508, pending 

 

UL 60950-1, 

pending

 

 

Class I Div 2, 

pending

 

IECEx

ATEX

II 3G Ex nA IIC T4 Gc 

pending

 

 

Marine, pending

 

 

EMC, LVD

 

Oct. 2013 / Rev. 1.0 DS-YR40.245-EN  
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 

www.pulspower.com   Phone +49 89 9278 0    Germany 

Содержание DIMENSION Y-Series

Страница 1: ...ry voltage Due to the low power losses the unit is very slender and only requires 46mm width on the DIN rail Large connection terminals allow for a safe and fast installation The large international a...

Страница 2: ...before the value represents a nominal voltage with standard tolerances usually 15 included E g DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 24Vdc A figure with the...

Страница 3: ...ed permanently with more than 50 of the rated output current Increase the side clearance to 15mm in case the adjacent device is a heat source e g another power supply See chapter 19 3 for other allowe...

Страница 4: ...22A in overload voltage 6V or short circuit mode Reverse current max 1mA at 24V per input 40 C to 70 C Reverse voltage max 40Vdc voltage applied to the output continuously allowed Output capacitance t...

Страница 5: ...equal current Power Losses typ 0 0 5 10 30 1 4 5 8W 40A 25 15 20 35 Output Current A 2 6 B 7 A 24V 25 C B 24V 60 C 3 V A QS40 set to 24V IIN UIN Output A V IOUT UOUT Variable Load 0 40A YR40 245 Input...

Страница 6: ...r specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can...

Страница 7: ...60950 1 SELV b Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient up to 70 C minimu...

Страница 8: ...structions Switch off circuit breaker 3a Remove plug 4 The plug prevents the cables from shorting Change power supply 1 or and redundancy module 2 Put the plug 4 back in Turn on the circuit breaker 3a...

Страница 9: ...on the top side of the housing with a ring type terminal ring cable lug which is suitable for a M4 screw Connection of the chassis is optional and not required since the unit fulfils the requirements...

Страница 10: ...defined limits Notes A test is not applicable according to EN 61000 6 2 since the device does not contain components susceptible to magnetic fields e g hall elements electrodynamic microphones etc EM...

Страница 11: ...ed directly from the low voltage mains IEC 60664 1 4 3 3 2 1 Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical su...

Страница 12: ...hm between housing and chassis ground terminal 14 DIELECTRIC STRENGTH The input and output voltages have the same reference are floating and have no ohmic connection to ground Type and factory tests a...

Страница 13: ...ation Class I Div 2 T4 Groups A B C D systems U S A ANSI ISA 12 12 01 2007 and Canada C22 2 No 213 M1987 Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc locations Number of ATEX certificate...

Страница 14: ...m The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation clearances See chapter 2 Fig 17 1 Front view Fig 17 2 Side view Oct 2013 Rev...

Страница 15: ...eways with or without utilizing a DIN Rail The two aluminum brackets and the black plastic slider of the unit have to be detached so that the steel brackets can be mounted For sideway DIN rail mountin...

Страница 16: ...on the bottom 5mm on the left and right sides when the device is loaded permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e...

Страница 17: ...lies and four YR40 245 redundancy modules Fig 19 2 Wiring diagram n 1 Redundancy 120A output current L N PE 24V 40A Parallel Use Single Use DC OK Power Supply AC Input L N PE 24V 40A Parallel Use Sing...

Страница 18: ...rve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 19 3 Mounting Orientation A Standard orientation YR40 245 Redundancy Module OUTPUT INPUT Output Curren...

Отзывы: