UC10.241, UC10.242

 

 

UC-Series 

24V,

 

15A,

 

CAPACITOR-BASED

 

DC-UPS 

 

 

11.

 

L

IFETIME 

E

XPECTANCY AND 

MTBF 

 

The lifetime expectancy of the DC-UPS is predominantly affected by the storage capacitors. The biggest influence in 
lifetime is a combination of operating voltage and operating temperature of these capacitors. To gain longest 
lifetimes, PULS does not utilize the full allowed working voltage for these capacitors and therefore accepts a slightly 
shorter buffer time. 

The EDLC’s do not experience a true end-of-life, rather the capacitance continually degrades over the life of the DC-
UPS. The typical degradation behavior resembles that of an exponential decay in the first couple of 1000 hours 
followed by a linear degradation. The majority of the capacitance reduction occurs during the initial use of the DC-UPS 
and this change in performance then levels off over time. When working with the specified lifetime numbers, the 
remaining capacity must always be taken into account. The buffer time correlates linearly to the capacity. 

The ultracapacitors have an almost unlimited shelf life (unlike batteries) when stored uncharged at 25°C. 

The number of charge/ discharge cycles does not have an impact on the lifetime as long as the number of cycles does 
not exceed 100 000. This should not be the case for a typical backup operation. 

 

Lifetime UC10.241

 

UC10.242

 

 

Remaining capacity 

85% 75% 85% 75% 

 

Lifetime expectancy 

*)

 

186 000h 

324 000h 

186 000h 

324 000h 

at 24V, 10A, 25°C 

 

155 000h 

270 000h 

155 000h 

270 000h 

at 24V, 15A, 25°C 

 

66 000h 

115 000h 

66 000h 

115 000h 

at 24V, 10A, 40°C 

 

55 000h  

96 000h 

55 000h  

96 000h 

at 24V, 15A, 40°C 

 

23 000h 

40 000h 

23 000h 

40 000h 

at 24V, 10A, 55°C 

 

19 000h 

34 000h 

19 000h 

34 000h 

at 24V, 15A, 55°C 

 

MTBF UC10.241

 

UC10.242

 

 

MTBF 

**)

  SN 29500, IEC 61709 

1 519 000h 

1 515 000h 

at 24V, 10A, 25°C 

 

1 443 000h 

1 439 000h 

at 24V, 15A, 25°C 

 

899 000h 

895 000h 

at 24V, 10A, 40°C 

 

854 000h 

850 000h 

at 24V, 15A, 40°C 

MTBF 

**)

  MIL HDBK 217F 

525 000h 

524 000h 

at 24V, 10A, 25°C; Ground Benign GB25 

 

498 000h 

497 000h 

at 24V, 15A, 25°C; Ground Benign GB25 

 

385 000h 

384 000h 

at 24V, 10A, 40°C; Ground Benign GB40 

 

365 000h 

364 000h 

at 24V, 15A, 40°C; Ground Benign GB40 

 

125 000h 

125 000h 

at 24V, 10A, 25°C; Ground Fixed GF25 

 

118 000h 

118 000h 

at 24V, 15A, 25°C; Ground Fixed GF25 

 

95 000h 

95 000h 

at 24V, 10A, 40°C; Ground Fixed GF40 

 

90 000h 

90 000h 

at 24V, 10A, 40°C; Ground Fixed GF40 

*)   The 

Lifetime expectancy

 shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 

expectancy of the built-in electrolytic capacitors and storage capacitors (ultracapacitors). Lifetime expectancy is specified in operational 
hours and is calculated according to the capacitor’s manufacturer specification. 

**) 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates reliability of a 

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 

 

The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 
has been running for 50 000h or only for 100h. 

 

May 2016 / Rev. 2.2 DS-UC10.241-EN 
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

12/27

Содержание DIMENSION UC Series

Страница 1: ...t this energy is released to the DC bus in a regulated process The DC UPSs are maintenance free and have a similar lifetime expectancy as power supplies No regular replacement of the capacitors is nec...

Страница 2: ...he publisher TERMINOLOGY AND ABREVIATIONS Normal mode Describes a condition where the capacitor is charged the input voltage is in range and the output is loaded within the allowed limits Buffer mode...

Страница 3: ...permanently with more than 50 of the rated power Increase this clearance to 15mm in case the adjacent device is a heat source e g a power supply Fig 2 1 Typical wiring diagram buffered branches non b...

Страница 4: ...A buffer current The transfer threshold voltage describes the input voltage where the unit switches into buffer mode and delivers output voltage from the capacitors if the input was above the turn on...

Страница 5: ...15A see Fig 4 2 Short circuit current min 17 9A load impedance 100mOhm see Fig 4 2 max 21 0A load impedance 100mOhm see Fig 4 2 Output capacitance typ 1 500 F included inside the DC UPS Capacitive an...

Страница 6: ...8 12 14 200mv 300mv Voltage drop Fig 4 3 Transition from buffer mode to normal mode and vice versa definitions Fig 4 4 Transfer behavior typ 500ms DIV 0V Output Voltage Input Voltage 24V 22 25V at 10...

Страница 7: ...after discharging with 1A until buffering stops Allowed number of charging discharging cycles no limitation no limitation Initial charging means that no input voltage was applied for several hours or...

Страница 8: ...680s at 0 5A buffer current typ 200s 400s at 1A buffer current typ 68s 136s at 3A buffer current typ 39s 78s at 5A buffer current typ 26s 53s at 7A buffer current typ 16 5s 33s at 10A buffer current...

Страница 9: ...ad min 1mA at 5Vdc min permissible load Isolation voltage 500Vac signal port to power port 8 INHIBIT INPUT The inhibit input disables buffering In normal mode a static signal is required In buffer mod...

Страница 10: ...Power Supply Output DC UPS Output full empty Capacitor Ready Contact closed open Buffering Contact closed open 5s 70s Example A The buffer event is longer than 1s and ends before the buffer capacitors...

Страница 11: ...pacitor fully charged typ 5 0W During charging 0A output current Fig 10 1 Efficiency vs output current in normal mode typ Fig 10 2 Power losses vs output current in normal mode typ Power losses versus...

Страница 12: ...10A 55 C 19 000h 34 000h 19 000h 34 000h at 24V 15A 55 C MTBF UC10 241 UC10 242 MTBF SN 29500 IEC 61709 1 519 000h 1 515 000h at 24V 10A 25 C 1 443 000h 1 439 000h at 24V 15A 25 C 899 000h 895 000h a...

Страница 13: ...9 50 A Remaining capacity A 85 B 75 B 15A Output Current 12 FUNCTIONAL DIAGRAM Fig 12 1 Functional diagram 24V Power Supply Boost Converter Step up Converter Charger Balancing Safety Circuits Input E...

Страница 14: ...onnecting a wire Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambient up to 45 C and 75 C for ambient up to 60 C and 90 C for ambient u...

Страница 15: ...Flashing pattern for the red warning LED Check input voltage 1 0 1 0 PC Mode activated AUU Input Terminals quick connect spring clamp terminal UUBUU Output Terminals quick connect spring clamp termina...

Страница 16: ...coupling clamp Criterions A DC UPS shows normal operation behavior within the defined limits EMC Emission According generic standards EN 61000 6 3 and EN 61000 6 4 Conducted emission IEC CISPR 16 1 2...

Страница 17: ...2103 EN 50178 not conductive LABS compatibility The unit does not release any silicone or other LABS critical substances and is suitable for use in paint shops Operational temperature is the same as t...

Страница 18: ...ve balancing circuit ensures uniform capacitor voltages If necessary the charging current will be reduced to a safe value Failing of one or more capacitor in the capacitor string included Ready contac...

Страница 19: ...TEX certificate EPS 15 ATEX 1 025 X The power supply must be built in in an IP54 enclosure EN 60079 0 EN 60079 15 ATEX II 3G Ex nA nC II T4 Gc Suitable for use in Class 1 Zone 2 Groups IIa IIb and IIc...

Страница 20: ...The DIN rail height must be added to the unit depth 127mm to calculate the total required installation depth Installation Clearances See chapter XX2XX Fig 21 1 Front view UC10 241 Fig 21 2 Front view...

Страница 21: ...s bracket is used to mount the DC UPS onto a flat surface without utilizing a DIN Rail UC10 241 UC10 242 May 2016 Rev 2 2 DS UC10 241 EN All parameters are specified at 24V 10A output current 25 C amb...

Страница 22: ...the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V branches which are s...

Страница 23: ...2 Wiring example for a fully redundant system redundant power supplies and redundant DC UPSs Power Supply 24V Output Power Supply 24V Output Load Failure Monitor YRM2 DIODE OUT IN 1 IN 2 IN 1 IN 2 23...

Страница 24: ...tic signal is required In buffer mode a pulse with a minimum length of 250ms is required to stop buffering The inhibit signal is stored and can be reset by cycling the input voltage For service purpos...

Страница 25: ...ontact closed External signal to start the delayed shut down Load open closed Buffering Contact open 1s full empty Capacitor Pin 7 8 open Ready Threshold 250ms Activation of the external control mode...

Страница 26: ...depends on the load current the lower the load current the lower the cut off voltage Considering this voltage range the energy can be calculated with the following formula full charge voltage U1 2 5V...

Страница 27: ...ee notes in section 2 first Symptom Action Check input voltage LED is on Check input voltage must be between 22 8V and 30V DC UPS did not buffer Inhibit input was set Capacitor did not have enough tim...

Отзывы: