PISA-B-8CL2-B1
PISA-B-8CL2-B4

Apr. 2021 / Rev. 0.1 DS-PISA-B-8CL2-Bx-xx-EN

www.pulspower.com

5 / 19

All parameters are specified at 24Vdc input voltage, 8x3.75A output currents, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

4.

DC-Input

The input can be powered from a regulated power supply or a similar DC source. Use an appropriately sized power supply,
which can deliver the required output current.

If a power supply with a continuous output current greater than 50A is used, a fuse or circuit breaker with 63A (B- or C-
Characteristic) must be connected between the power supply and the electronic fuse module.

The continuous voltage between the input and ground must not exceed 60Vdc.

The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order to maintain SELV or
PELV outputs.

Check for correct input polarity. The device will not operate when the voltage is reversed.

Input voltage

nom.

DC 24V

-20%/+25%

Input voltage range

19.2-30Vdc

typ.

19Vdc

Input voltage required to
switch on the outputs

max.

19.6Vdc

Input current

max.

40A

For multiple modules connected via power-bus-bar

max.

30A

For a single module at fully loaded outputs

Stand-by current with no load current on the outputs

Internal current
consumption

typ.

40mA

For PISA-B-8CL2-B1

typ.

35mA

For PISA-B-8CL2-B4

5.

Output

The output can supply any kind of loads, including inductive and capacitive loads. The maximum size of capacitive loads is
specified in the table below (see Tab. 5-1). Larger load capacitors might result in an unintended turn-off of the channel.
More detailed information regarding allowable capacitive loads is available on request. If in doubt or when you do not
know the input capacitance of your load, we recommend to perform tests with the real load.

The outputs of each channel fulfil the requirements for a limited power source acc. to NEC Class 2.

Output channels can be switched on and off separately by pushing the corresponding control button for longer than 50ms.
A switched off channel is displayed with the uppermost red LED of the LED bar graph. Factory setting is that all channels
are switched on.

Channels 1 and 2 have a current limited output, while channels 3 to 8 have an overcurrent shutdown behaviour only.

– Do not apply reverse voltages from the load to the output terminals that are higher than 30V and last longer than 1s.
– Do not parallel outputs for higher output currents.
– Do not connect outputs in a series connection for higher output voltages.
– Do not connect batteries for charging purposes to the output of the device.

In order to avoid too high peak currents on the 24V supply when applying the 24V supply voltage, the output channels are
switched on in delayed steps. Channel 1 switches on after 50ms followed by the remaining channels with a delay of 100ms
each. This scheme applies when all channels are switched on. Channels that are switched off are skipped.

Fig. 5-1: Turn-On sequence after applying an input voltage

Содержание DIMENSION PISA-B-8CL2-B1

Страница 1: ...1 is equipped with a common tripping signaling relay contact that reports tripped channels while the PISA B 8CL2 B4 has a digital coded signal output built in for this function All PISA B devices are...

Страница 2: ...anging the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this document...

Страница 3: ...acts of the devices Use an appropriately sized 24V power supply which can deliver the peak current required to trip the load channels If peak currents are too low the supply voltage for the protection...

Страница 4: ...he power bus bar of 32A is not exceeded Fuse modules can be lined up on the DIN rail without spacing The power bus bars can be plugged in from the front and must have a length that all plug contacts o...

Страница 5: ...tive and capacitive loads The maximum size of capacitive loads is specified in the table below see Tab 5 1 Larger load capacitors might result in an unintended turn off of the channel More detailed in...

Страница 6: ...typ 120mV For CH1 or CH2 when all channels are loaded with 3 75A typ 60mV For CH3 to CH8 at 3 75A load when all other channels are not loaded typ 135mV For CH3 to CH8 when all channels are loaded with...

Страница 7: ...ry setting is Fast Tripping delay typ 1 1s For all channels in Slow mode at 1 5x nominal current typ 0 22s For all channels in Fast mode at 1 5x nominal current typ 2ms 1 1s For CH1 and CH2 in short c...

Страница 8: ...n for channel 3 at the same time The selected option is shown on the LED matrix for 2 seconds Letter F indicates the fast and the letter S the slow tripping characteristic If only the SET button is pr...

Страница 9: ...with 40 60 of the nominal current Channel 7 is loaded with 0 10 of the nominal current Channel 8 has tripped due to over current 8 Digital Coded Interface PISA B 8CL2 B4 The device is equipped with a...

Страница 10: ...voltage see chapter 19 10 Reset Input A restart of switched off channels can be done either by a button on the unit or by a control signal on the reset input pins 11 12 Therefore push the correspondi...

Страница 11: ...pulspower com 11 19 All parameters are specified at 24Vdc input voltage 8x3 75A output currents 25 C ambient and after a 5 minutes run in time unless otherwise noted 12 Functional Diagram Fig 12 1 Fu...

Страница 12: ...for positive input power bus bar E2 Interconnection for negative return input power bus bar F Set button required for controlling the unit G Channel control buttons Fig 13 1 Front side H LED matrix d...

Страница 13: ...8A and 40 C t b d At 24V 8x3 75A and 25 C t b d At 24V 8x1 88A and 25 C 16 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates rel...

Страница 14: ...iterion A Output lines 2kV Criterion A Surge voltage on input lines EN 61000 4 5 500V Criterion B housing 1kV Criterion B Surge voltage on output lines EN 61000 4 5 500V Criterion B housing 1kV Criter...

Страница 15: ...Humidity 5 to 95 r h According to IEC 60068 2 30 Atmospheric pressure 110 54kPa See Fig 18 2 for details Altitude Up to 5000m 16 400ft See Fig 18 2 for details Over voltage category N A Impulse withs...

Страница 16: ...max 500Vac Power port to signal port max 500Vac Power port signal port to housing Class of protection III A PE Protective Earth connection is not required Degree of protection IP20 According to EN IE...

Страница 17: ...control and laboratory use Particular requirements for control equipment Applicable for US and Canada E File E198865 UL 2367 UL Certificate Recognized component for category QVRQ UL 2367 Standard for...

Страница 18: ...130mm 5 12 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 370g 0 82lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with...

Страница 19: ...upply of the 24V is then only done by one fuse module preferably in the middle because the current is then better distributed in both directions and the permissible current of the power bus bars of 32...

Отзывы: