ML60.122
MiniLine-2
12V,
4.5A,
S
INGLE
P
HASE
I
NPUT
P
OWER
S
UPPLY
100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efficiency up to 87.6%
Low No-load Losses and Excellent Partial-load Efficiency
Compact Design, Width only 45mm
Electronic Inrush Current Limitation
Operation down to -40°C
Full Output Power up to +60°C
Large International Approval Package
3 Year Warranty
1/23
G
ENERAL
D
ESCRIPTION
A compact size, light weight, simple mounting onto the
DIN-rail and the utilization of only quality components
are what makes the MiniLine power supplies so easy to
use and install within seconds.
A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains provides reliable output power. This offers
superior protection for equipment which is connected
to the public mains network or is exposed to a critical
industrial environment.
The MiniLine series offers output voltages from 5 to
56Vdc and a power rating from 15W to 120W.
The specialty of the ML60.122 is the electronic inrush
current limitation and the suitability for very low
ambient temperatures. The unit is fully specified down
to -40°C.
The supplementary MiniLine decoupling diode module
MLY10.241 allows building of redundant systems or to
protect against back-feeding voltages.
S
HORT
-
FORM
D
ATA
Output voltage
DC 12V
Adjustment range
12 - 15V
Output current
4.5A at 12V
3.6A at 15V
Output power
54W
Output ripple
< 50mVpp
20Hz to 20MHz
Input voltage
AC 100-240V
-15% / +10%
AC 100V mains
requires derating
Mains frequency
50-60Hz
±6%
AC Input current
0.97 / 0.61A
at 120 / 230Vac
Power factor
0.54 / 0.44
at 120 / 230Vac
AC Inrush current
typ. 6A
input voltage
and temperature
independent
DC Input
88-375Vdc
below 130Vdc
derating required
Efficiency
85.8 / 87.6%
at 120 / 230Vac
Losses
8.9 / 7.6W
at 120 / 230Vac
Temperature range -40°C to +70°C
operational
Derating
1.4W/°C
+60 to +70°C
Hold-up time
typ. 25 / 113ms
at 120 / 230Vac
Dimensions 45x75x91mm
WxHxD
Weight
250g / 0.55lb
O
RDER
N
UMBERS
Power Supply
ML60.122
12-15V Standard unit
Accessory MLY10.241
Redundancy
Module
ZM3.WALL
Wall
mount
bracket
M
ARKINGS
Ind. Cont. Eq. UL 508
UL 60950-1
Marine
Class I Div 2
NEC
Class 2
EMC, LVD
Nov. 2015 / Rev. 1.4 DS--ML60.122-EN
All parameters are specified at 12V, 4.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany