ARV 2000

 

 

Section 1: Installation Information, Checklist & General 

Descriptions 

 

12755 rev 04 

            Page 1 of 5 

1.1  Installation Information 

Important

 

The ARV 2000 uses single-stage regulation to control pressure in non-critical processes. The valve 
compensates for house exhaust fluctuations, reduces potential for contamination, and provides quick 
response, as well as being low maintenance and self-cleaning. The ARV 2000 has been manufactured 
to provide pressure control in the range of 0-498.2 Pascal’s (50.8 mm H

2

O). The total ARV 2000 system 

is comprised of the tool Interface module (TIM-100 FSP) controller, the ARV 2000 valve, and 
associated interface cables. The TIM-100 FSP controls a stepper-motor driven throttling-type valve, 
which regulates the pressure drop across the valve, resulting in tighter controls of airflow and pressure 
at the valve input (i.e., process) pressure.  

 

 

 

 

 

Comparison

 

with

 

Traditional

 

Butterfly

 

Valves

 

and

 

Double

-

Acting

 

Gate

 

Valves

 

The ARV 2000 differs from traditional valves in several ways. The most important feature is its linearity, 
which derives from the vane configuration. As a butterfly valve or gate valve reaches its nearly closed 
position, small rotational increments create large differences in the open area through the valve 
resulting in large changes in the flow through the valve. As the valve opens, the flow changes less and 
less with each rotational step. The ARV 2000, on the other hand, closes off the same amount of area 
with each step, so the flow is reduced by the same amount at each step.  

The non-linearity of the traditional valve prevents it from controlling well at the maximum and minimum 
of its range. The ARV 2000, on the other hand, controls well throughout its range. 

The second major difference between a butterfly valve and an ARV 2000 is Fast Set Point control 
technology that creates a rapid response to set point not achievable with conventional PID control.  

System

 

compatibility

 

The ARV 2000 system electronics provide significant flexibility. Since the same electronics, with 
minimal configuration changes entered from the keypad, can be used to control Progressive 
Technologies’ automated VRV and automated SENTRY products, the pressure control technology can 
be upgraded at any time with minimal effort and expense.  

 

 

 

 

 

 

 

 

 

 

Air Flow Through The Process And Control System 

Clean room         

Process 

ARV 

2000 

Exhaust
 

Содержание ARV 2000

Страница 1: ...derives from the vane configuration As a butterfly valve or gate valve reaches its nearly closed position small rotational increments create large differences in the open area through the valve result...

Страница 2: ...Checklist Preparation 1 Unpack and Review Part Names 2 Copy or Print Installation Checklist on Clean Room Paper 3 Review Installation and Layout Guidelines Installation Power Up 4 ARV 2000 Align the...

Страница 3: ...ed Report the missing or damaged components to PTI customer support department at 1 978 863 1000 TIM 100 FSP to ARV 2000 Cable Tool Host to TIM 100 FSP Interface Cable SENTRY OR Stand Alone Power Supp...

Страница 4: ...2 External sense port Not used for future applications 3 Reference port do not block references the clean room pressure This port connects directly to the internal pressure transducer 4 Auxiliary sen...

Страница 5: ...djust the display contrast 6 Power Interface Port accepts the power cable power supply or power and interface cable 7 RS 422 485 Port accepts the optional serial communication cable 8 On Off Switch is...

Страница 6: ...Only the process exhaust to be controlled should be plumbed to the ARV 2000 Other sources of exhausted airflow or manifolds should not be connected prior to the ARV 2000 input 3 If a drain is used fo...

Страница 7: ...requires a minimum of 170 Pa or the equivalent of your set point whichever is more negative of facility exhaust at the rated flow capacity to operate properly It is recommended that all upstream and d...

Страница 8: ...0 requires the TIM 100 FSP The user interfaces with the TIM 100 FSP directly or through the tool controller to enter set points and other critical information With feedback from the transducer the TIM...

Страница 9: ...after eight weeks and adjusting the cleaning frequency as necessary based on this inspection If particles or foreign matter appear to be interfering with proper operation of the ARV 2000 system follo...

Страница 10: ...log Interface Analog interface improperly installed Properly install analog interface cable Serial Interface Serial cable improperly installed or address not set Properly install communication cable A...

Страница 11: ...nt Change 0 5 Seconds Response to H E Fluctuation 0 5 Seconds Response from Open to Close 1 5 Seconds Installation duct length process to ARV 10 Meters Chemical Compatibility Low Concentrations of Sol...

Страница 12: ...iltRate 0 Disp 0 Sentry Ver LookBand 256 Disp 1 Pres SP Usage1 R 5 Disp 2 Pres Usage2 R Usage3 R Usage4 R Select X APPLICATION SPECIFIC MENU PARAMETER SETTINGS TIM FSP P N Menu Item Default Value X N...

Страница 13: ...12755 Rev 04 Page 3 of 3 4 3 Grounding Recommended System Grounding P T NC I ROGRESSIVE ECHNOLOGIES...

Страница 14: ...erial Communication Cable Part Number ______________ Revision ______________ Other Special Technical Support Calls If you are having difficulty troubleshooting this product please contact the PTI tech...

Страница 15: ...eventive maintenance failure of or caused by parts not supplied by PTI failure of or improper electrical power alteration or modification transportation vandalism fire chemicals or other casualty caus...

Отзывы: